Electric motors for explosive atmospheres | 5 

Component

Classified area marked on 

nameplate

Classified area where product 

will be installed

Maximum operating temperature (°C)

Alarm

Tripping

Winding

Ex d

Ex d

130

150

Ex n

Ex n

130

155

Ex t

Ex t

120

140

Ex e

Ex e

-

110

Ex n + Ex t

Ex n

140

155

Ex t

-

140

Ex d + Ex t

Ex d

140

150

Ex t

-

140

Class I Div. 1

Class I Div. 1

130

150

Class I Div. 2

Class I Div. 2

130

155

Class II Div. 1

Class II Div. 1

120

140

Bearings

All

All

110

120

Table 5

 - Maximum temperature of actuation for thermal protections

Notes:

1)  The quantity and type of thermal protections installed in the motor are infomed in the additional nameplates included on it.
2)  In case of calibrated thermal protection (for example, Pt-100), the monitoring system must be set at the operation temperature indicated on Table 5.

In “Ex e” motors application, the thermal protection device, in case of overload or locked rotor, must actuate with time delay according to the 
current and track the external power cables. The “

t

E

” time indicated in the motor nameplate can not be exceeded. The “Ex e” motors, submitted to 

acceleration time conditions greater than 1,7 x “

t

E

” time, must be protected with protection devices against overcurrent. 

Motors fitted with Automatic Thermal Protectors will reset automatically as soon as the motor cools down. Thus, do not use 

motors with Automatic Thermal Protection in applications where the auto-reseting of this device may cause injuries to people or 

damage to equipment. If the Automatic Thermal Protector trips, disconnect the motor from the power supply and check the cause 

why the thermal protector trips. 

For information about the use of variable frequency drives, you must follow the instructions in the documents 50034162 (“Installation, Operation and 
Maintenance Manual of Electric Motors for Use in Explosive Atmospheres”) and 50029350 (“Induction motors fed by PWM frequency inverters” in the 
website www.weg.net and in the manual of the variable frequency drive. 

 

4. OPERATION

During operation, do not touch the non-insulated energized parts and never touch or stay too close to rotating parts.
Ensure that the space heater is always OFF during the motor operation.

The rated performance values and the operating conditions are specified on the motor nameplate. The voltage and frequency variations of the power supply should 
never exceed the limits established in the applicable standards.
Occasional different behavior during the normal operation (actuation of thermal protections, noise level, vibration level, temperature and current increase) must always 
be assessed by qualified personnel. In case of doubt, turn off the motor immediately and contact the nearest WEG service center.
Do not use roller bearings for direct coupling. Motors fitted with roller bearings require a minimum radial load to ensure a proper operation.
For motors fitted with oil lubrication or oil mist systems, the cooling system must be ON even after the machine is OFF and until the machine is at complete standstill.
In case of failure in the lubrication and/or cooling system, turn the motor OFF immediatly.
After complete standstill, the cooling and lubrication systems (if any exist) must be switched OFF and the space heaters (if available) must be switched ON.
In case of doubts, turn the motor OFF immediately and contact the nearest WEG authorized service Center for explosive atmospheres.

5. MAINTENANCE

Before any service is performed, ensure that motor is at standstill, disconnected from the power supply and protected against 

accidental energization. Even when the motor is stopped, dangerous voltages may be present in space heater terminals.

Motor disassemble during the warranty period must be performed by a WEG authorized service center for Explosive Atmospheres only.

For motors with permanent magnet rotor (lines W22 Quattro and W22 Magnet), the motor assembly and disassembly require the 

use of proper devices due to the attractive or repulsive forces that occur between metallic parts.  This job must be only performed by 

a WEG Authorized service center specifically trained for such an operation. People with pacemakers cannot handle these motors. The 

permanent magnets can also cause disturbances or damages to other electric equipment and components during maintenance.

Motors with flameproof enclosures and Protection by enclosure (Ex t), wait at least 60 minutes for frame sizes IEC 71 up to 200 and NEMA 

143/5 up to 324/6 and at least 150 minutes for frames sizes IEC 225 up to 355 and NEMA 364/5 to 586/7 to open the terminal box and/or 

disassemble the motor.

For the W50 and HGF motor lines provided with axial fans, the motor and the axial fan have different markings for indicating the direction 

of rotation for prevent incorrect assembly. The axial fan must be assembled so that the indicative arrow for direction of rotation is always 

visible, viewing the non-drive end side. The marking indicated on the axial fan blade, CW for clockwise direction of rotation or CCW for 

counterclockwise direction of rotation, indicates the direction of rotation of the motor viewing the drive end side.

Motors with degree of protection greater than IP55 are supplied with a sealing product on joints and fixing bolts. Before assembly the components 

with machined faces (for example, terminal box cover of Flameproof motors), clean these surfaces and apply a new layer of this product.

For Flameproof motors joints only the following products can be used: Lumomoly PT/4 (manufacturer: Lumobras – for ambient temperature ranging 

from -20 °C to +80 °C) or Molykote DC 33 (manufacturer: Dow Corning – for ambient temperature ranging from -55 °C to +80 °C)). For motors with 

other types of protection, use Loctite 5923 (manufacturer: Henkel) on joints. 

For Flameproof motors, special care should be taken with the machined surfaces of the flame path. These surfaces must be free of burrs, scratches, 

etc. that reduce the flame path length and increase the gap. The gaps between terminal boxes and the respective terminal box covers should not 

exceed the values specified in Table 6.

Table 6

 - Maximum gap between terminal box and terminal box cover for flameproof enclosures

Product line

Frame size

Flat joint

Cylindrical joint

Gap (max)

Lenght (min)

Gap (max)

Lenght (min)

W21Xd

IEC 90 to 355 

NEMA 143 to 586/7

0.05 mm

Under request

Not available

W22Xd

IEC 71 and 80

Not available

0.15 mm

12.5 mm

IEC 90 to 355 

NEMA 143 to 586/7

0.075 mm

6 mm

0.15 mm

19 mm

For terminal box cover mounting, please follow the tightening torques indicated on Table 2 for fixing bolts.

In case of replacement of a fixing bolt, it is necessary to keep its dimensions and quality of material. For flameproof motors, the yield stress of the fastener 

elements of motor and terminal boxes enclosures must be at least equal to class 12.9 for carbon steel bolts and class A2-70 or A4-70 for stainless steel bolts.

Motors which may have a potential risk of electrostatic charge accumulation, supplied duly identified, must receive proper cleaning and maintenance 

interventions, i.e. with the use of a damp cloth, avoiding electrostatic discharges.

For Protection by Enclosure motors (groups I and/or III), the maximum permissible dust layer on the motor enclosure is five millimeters (5 mm).

Regularly inspect the operation of the motor, according to its application, and ensure a free air flow. Inspect the seals, the fastening bolts, the bearings, 

the vibration and noise levels, the drain operation, etc.

The lubrication interval is specified on the motor nameplate (more information in the manual 50034162 in the website 

www.weg.net

).

Summary of Contents for W21Xd

Page 1: ...ctricos para atm sferas explosivas Manual de instalaci n operaci n y mantenimiento de motores el ctricos Elektrische motoren voor explosiegevaarlijke omgevingen Handleiding voor installatie bediening...

Page 2: ...EN 60079 15 2010 EN 60079 31 2014 EN 60204 1 2006 A1 2009 AC 2010 and EN 60204 11 2000 AC 2010 A comparison of the current version of the EN 60079 0 2012 A11 2013 EN 60079 1 2014 EN 60079 15 2010 and...

Page 3: ...against dust vibrations gases and corrosive agents with relative humidity not over 60 In order to prevent water condensation within the motor during the storage period it is recommended to keep the sp...

Page 4: ...ust be fitted with components such as cable glands and conduits that meet the applicable standards and regulations for each country For Ex d motors the conduit entries are permitted only for electrica...

Page 5: ...y period must be performed by a WEG authorized service center for Explosive Atmospheres only For motors with permanent magnet rotor lines W22 Quattro and W22 Magnet the motor assembly and disassembly...

Page 6: ...es extend the equipment warranty period WEG s Civil Liability is limited to the supplied product WEG will not be liable for indirect or consequential damages such as losses of profit and revenue losse...

Page 7: ...ala o do motor A n o ser que haja especifica o ao contr rio no pedido de compra os motores WEG s o balanceados dinamicamente com meia chaveta e em vazio desacoplados Os elementos de transmiss o como p...

Page 8: ...segura que garanta o m nimo n vel de prote o EPL Gb Verifique o correto funcionamento dos acess rios freio encoder prote o t rmica ventila o for ada etc instalados no motor antes de coloc lo em opera...

Page 9: ...plos o e suas respectivas tampas a folga entre as mesmas n o deve exceder os valores indicados na Tabela 6 Tabela 6 Folga m xima entre tampa e caixa de liga o para motores prova de explos o Linha de p...

Page 10: ...clasificaci n del rea de instalaci n y de las caracter sticas del ambiente es de responsabilidad del usuario Los motores el ctricos tienen circuitos bajo tensi n y componentes giratorios que pueden ca...

Page 11: ...las normas vigentes y que la conexi n est bien apretada Conecte el motor correctamente a la red el ctrica a trav s de contactos seguros y permanentes siguiendo siempre los datos mostrados en la placa...

Page 12: ...conexi n Bobinado Ex d Ex d 130 150 Ex n Ex n 130 155 Ex t Ex t 120 140 Ex e Ex e 110 Ex n Ex t Ex n 140 155 Ex t 140 Ex d Ex t Ex d 140 150 Ex t 140 Class I Div 1 Class I Div 1 130 150 Class I Div 2...

Page 13: ...ccione peri dicamente el funcionamiento del motor seg n su aplicaci n asegur ndose de que el aire fluya libremente Inspeccione los sellos los tornillos de fijaci n los cojinetes los niveles de vibraci...

Page 14: ...enen Angaben m ssen denen der Rechnung der Betriebsumgebungsbedingungen in welcher der Motor eingesetzt wird und der Z ndschutzart dem Ger teschutzniveau EPL entsprechen Wird der Motor nicht sofort in...

Page 15: ...fen geliefert d rfen diese Motoren nur in den Gruppen IIB IIC und IIIC f r Umgebungstemperaturen von 55 C bis 40 C und in der Temperaturklassen T5 bis T2 eingesetzt werden F r Gruppen IIIC muss die Sc...

Page 16: ...der blockiertem Motor mit Verz gerung in Abh ngigkeit der Motorspannung ansprechen und die externen Versorgungskabel indirekt berwachen Die auf dem Typenschild angegebene Zeit tE darf nicht berschritt...

Page 17: ...er Transport Lagerung Handhabung Installation Betrieb und Wartung der Elektromotoren steht Ihnen die Webseite www weg net zur Verf gung Auch f r Motoren mit Sonderanwendungen oder erschwerten Betriebs...

Page 18: ...teur n est pas install tout de suite le stocker dans un endroit sec exempt de poussi re de vibrations de gaz et d agents abrasifs et avec une humidit relative de l air inf rieure 60 Afin d viter la co...

Page 19: ...5 6 6 8 6 8 6 8 6 8 6 8 6 8 M tallique 40 50 40 50 55 70 65 80 100 120 115 140 150 175 200 240 Le moteur doit toujours tre positionn de sorte que le trou de drainage se trouve la position la plus bas...

Page 20: ...n est pas recommand e Les moteurs quip s de roulement rouleaux ont besoin d une charge radiale minimum pour un fonctionnement satisfaisant Lors de l arr t d un moteur quip de syst mes de lubrification...

Page 21: ...iode de garantie diff rente est d finie dans la proposition technico commerciale d une vente particuli re elle remplacera les d lais dict s ci dessus Les d lais de garantie tablis ci dessus sont ind p...

Page 22: ...for explosive atmospheres 22 1 WEG g g g g Ex e g Ex n g Ex d Ex de g Ex t g Class I Division 1 g Class I Division 2 g Class II Division 1 g Class II Division 2 50034162 www weg net WEG EPL X 2 WEG 6...

Page 23: ...5 30 30 50 50 75 Ex de 1 1 5 2 4 4 6 5 6 5 9 5 9 10 15 20 30 3 7 4 8 7 11 2 6 6 10 Ex n Ex t Ex e 3 5 4 8 8 15 18 30 25 40 30 45 35 50 1 5 3 3 5 5 10 10 18 28 40 45 70 115 170 1 1 5 2 4 4 6 5 6 5 9 1...

Page 24: ...5 5 C Ex d Ex d 130 150 Ex n Ex n 130 155 Ex t Ex t 120 140 Ex e Ex e 110 Ex n Ex t Ex n 140 155 Ex t 140 Ex d Ex t Ex d 140 150 Ex t 140 Class I Div 1 Class I Div 1 130 150 Class I Div 2 Class I Div...

Page 25: ...ote DC 33 Dow Corning 55 C 80 C Loctite 5923 Henkel 6 6 W21Xd 90 355 NEMA 143 586 7 0 05 W22Xd 71 80 0 15 12 5 90 355 NEMA 143 586 8 0 075 6 0 15 19 2 12 9 A2 70 A4 70 I III 5 6 7 W22Xd W22Xt W22Xn 12...

Page 26: ...chermingtype en het EPL van de motor Indien de motor niet onmiddellijk wordt ge nstalleerd raden wij u aan de motor te bewaren in een schone en droge plaats vrij van stof trillingen en agressieve chem...

Page 27: ...nder anderen de nominale motorstroom de bedrijfsfactor en de lengte van de kabels Voor motoren zonder klemmenbord isoleer de eindkabels van de motor met behulp van isolatiematerialen in overeenstemmin...

Page 28: ...atie over het gebruik van de frequentieomvormer moet men verplicht de instructies volgen van de handleiding van de motor op de site www weg net en van de handleiding van de frequentieomvormer 4 BEDIEN...

Page 29: ...Motors Business Unit WEG biedt garantie tegen defecten in het geleverde werk en materiaal van zijn producten De garantie is geldig gedurende 18 maanden gerekend vanaf de factuurdatum van de fabriek of...

Page 30: ...cui il motore verr installato al tipo di protezione e al tipo di EPL del motore Nel caso in cui il motore non dovesse venir installato immediatamente si raccomanda di conservarlo in luogo pulito e asc...

Page 31: ...ando viene utilizzato il terminale tutti i fili che formano il cavo multifilo devono essere fissati all interno della guaina L isolamento dei cavi degli accessori dev essere tenuto ad una distanza mas...

Page 32: ...ire scollegare il motore dalla rete elettrica e verificare la causa per cui intervenuta la protezione termica Per ulteriori informazioni circa l uso del convertitore di frequenza obbligatorio seguire...

Page 33: ...TERMINI DI GARANZIA WEG Equipamentos El tricos S A Divisione motori WEG offre una garanzia che copre i difetti di mano d opera e materiali per i propri prodotti per un periodo di 18 mesi a decorrere...

Page 34: ...g Ex e g n Ex n g Ex d Ex de g Ex t g Class I Div 1 g Class I Div 2 g Class II Div 1 g Class II Div 2 50034162 www weg net WEG www weg net EPL X 2 WEG 60 5 ISOVG68 3 WEG IP55 IP56 IP65 IP66 20 C 40 C...

Page 35: ...1 2 NPT 2 NPT 2 1 2 NPT 3 NPT 4 NPT 5 6 6 8 6 8 6 8 6 8 6 8 6 8 40 50 40 50 55 70 65 80 100 120 115 140 150 175 200 240 W A12 W B12 160V W B12 500V 1 1 2 Nm 3 Nm 3 4 mm EPL IP Ex d II 5 Ex n Ex ec Ex...

Page 36: ...2 18 WEG WEG WEG WEG WEG WEG WEP WEG WEG WEG 4 WEG 5 WEG W22 Quattro W22 Magnet WEG 60 IEC 71 200 NEMA 143 5 324 6 150 IEC 225 355 NEMA 364 5 586 7 W50 HGF IP55 Lumomoly PT 4 Lumobras 20 C 80 C Molyko...

Page 37: ...Ex nA IIC T3 Gc IECEx BAS 10 0104X 315 450 W50X Ex nA IIC T3 Gc IECEx BAS 10 0104X 63 355 W21 Ex t Ex tc IIIB T125 C Dc IECEx BAS 10 0045X 63 355 W21 Ex t Ex tb IIIC T125 C Db IECEx BAS 10 0099X W22X...

Page 38: ...I Mb X 1Ex d e IIA IIB IIC T4 T6 Gb X Ex d e I Mc X 225 280 1Ex d IIB T2 T6 Gb X PB Ex d I Mb X 1Ex d e IIB T2 T6 Gb X Ex d e I Mc X 55 C Ta 80 C TC RU C BR AA87 B 00697 225 355 1Ex d IIC T2 T6 Gb X...

Page 39: ...eefa14ATEX0208X II 2G Ex de I IIB IIC T4 Gb 20 C Ta 80 C 280 355 II 2G Ex db IIB T4 Gb 20 C Ta 80 C Baseefa15ATEX0152X II 2G Ex db eb IIB T4 Gb 20 C Ta 80 C I M2 Ex db I T4 Mb II 2G Ex db IIB or IIC T...

Page 40: ...RRARI S R L Via Cremona 25 26015 Soresina CR Cremona Phone 39 374 340 404 www ferrarisrl it STIAVELLI IRIO S P A Via Pantano Blocco 16 Capalle 50010 Campi Bisenzio FI Phone 39 55 898 448 www stiavelli...

Reviews: