85
Dimming Confi guration
DIMMING CONFIGURATION
Dimming Confi guration enables communication
between the load and the LMCT-100. Use this
function to change dimming parameters.
Refer to the DLM Dimming System Addendum for
further information and system requirements.
Load 1 quickly turns ON and OFF (or OFF and ON
depending on its original state).
Based on the room controller type (Dim or Switch)
one of the following screens is presented for load 1.
Important:
All loads connected to dimming capable
room controllers default to Load Type <Dim>. Be
sure to select the appropriate load type because
these room controllers can control either type of
load. Default settings are based on the load type
selected.
Press
Select
Press
Select
P o i n t t o a n y I R
e n a b l e d d e v i c e o n
t h e n e t w o r k
P r e s s ‘ S e l e c t ’
S e n s o r C o n fi g u r a t i o n
L o a d C o n fi g ( P n L )
D a y l i g h t i n g C o n fi g
B u t t o n C o n fi g u r a t i o n
D i m m i n g C o n fi g u r a t i o n
M o r e
=
B AT
L o a d 1 D i m C o n fi g
Ty p e :
< D i m >
L o w Tr i m :
< 0 % >
H i g h Tr i m :
< 1 0 0 % >
P re s e t L e v e l :
< L a s t >
B u r n - i n H o u r s :
< 0 >
S E N D P R I O R N E X T
Type: Dimming
L o a d 1 D i m C o n fi g
Ty p e :
< S w i t c h >
Tr i p P o i n t :
< 5 1 % >
( Tr i p p o i n t a l t e r s
w h e n a re l a y s w i t c h e s
d u r i n g a f a d e )
S E N D P R I O R N E X T
Type: ON/OFF Switch
Choose
Load Type:
Dim or Switch
Press
Choose
Load Type:
Dim or Switch
Press