49
Calibration (LMLS-600 Only)
Manual Calibration
Manual Calibration allows you to refi ne the setpoint
for the controlled zone.
NOTE
: Even if you wish to refi ne the setpoints using
the Manual Calibration feature, you MUST fi rst
complete an Automatic Calibration to establish the
other critical installation parameters.
Press
Select
Press
Select
L M L S - 6 0 0 0 2 9 3 6 1 1 9 3 5
Z o n e S e t u p
C a l i b r a t i o n
Z o n e S e t t i n g s
A d v a n c e d S e t t i n g s
C o n t r o l M o d e
Choose
Manual
Calibration
Choose
Calibration
D a y l i g h t i n g L M L S - 6 0 0
A u t o m a t i c C a l i b r a t i o n
M a n u a l C a l i b r a t i o n
Choose a reference location within the daylighting
zone that is most likely to have the lowest light level
when daylit and is located farthest from the window.
P o i n t t o a n y I R
e n a b l e d d e v i c e o n
t h e n e t w o r k
P r e s s S e l e c t
C a l i b r a t i n g L M L S - 6 0 0
D e s i r e d L i g h t L e v e l
a t t h e w o r k p l a n e : < 5 0 f c >
A c t u a l L i g h t L e v e l a t
a t t h e w o r k p l a n e : < 3 5 f c >
S E N D
Press
Select
To set the Dimming and On and Off Setpoints
automatically to best match a designed light level
for the workplane, enter the desired level, along
with the present measured level (from a light
meter), and then press SEND.