Advanced Settings (LMLS-400/LMLS-500)
Hold Off
The Hold Off setting
selects the behavior of
daylighting loads when
they are turned ON, by
a switch or occupancy
sensor.
If Hold Off = <No> (default), the loads can always be
turned on to their previous level, and then will begin
to adjust based upon daylight.
If Hold Off = <Yes>, the sensor will limit the loads to
the level presently allowed by daylight contribution.
This means that the loads may not initially turn ON
(if the ambient light level is high - above the ON
or Dimming Setpoint), but will become active for
daylighting control, and will turn ON or dim up as
daylight contribution drops.”
Scenes Stop DL
When set to No,
the sensor allows
daylighting to adjust
light levels, up to the
level recorded in the
Scene, even though a
scene is active. When set to Yes, daylighting control
is disabled for any loads on which a scene is recalled
until a change is manually made to the level of a
load in the zone, or until the next cycle of occupancy.
D a y l i g h t i n g L M L S - 4 0 0
S E N D
L i g h t L e v e l :
A l l o w O v e r r i d e :
O v e r r i d e T i m e :
H o l d O f f :
S c e n e s S t o p D L :
I g n o r e A f t H r s :
1 0 f c
< Ye s >
< I n fi n >
< N o >
< N o >
< N o >
D a y l i g h t i n g L M L S - 4 0 0
S E N D
L i g h t L e v e l :
A l l o w O v e r r i d e :
O v e r r i d e T i m e :
H o l d O f f :
S c e n e s S t o p D L :
I g n o r e A f t H r s :
3 0 0 f c
< Ye s >
< I n fi n >
< N o >
< N o >
< N o >