Dimming Confi guration
Burn-in
This feature allows the user
to burn-in, or season, all of
the lamps associated with
the load. This is most often
done to fl uorescent lamps
to insure stabilization of
the lamp and/or dimming
compatibility.
The value options are 0, 12 or 100 hours. If 12 or 100
hours is entered, then the associated lights remain
at 100% light level at any time they are turned ON
until the number of hours have elapsed. The light
may be turned ON or OFF as desired, however they
do not respond to dimming during this time.
Send
Choosing Send and pressing Select saves the new
settings to load 1. After pressing select, the “Point
to any IR enabled device” screen is presented. From
this screen you can either confi gure another load or
exit Dimming Confi guration by pressing the HOME
or BACK buttons.
L o a d 1 D i m C o n fi g
Ty p e : < D i m >
L o w Tr i m :
< 0 % >
H i g h Tr i m :
< 1 0 0 % >
P re s e t L e v e l :
< L a s t >
B u r n - i n H o u r s :
< 1 0 0 >
S E N D P R I O R N E X T
Choose Burn-in Hours
<0, 12 or 100>
L o a d 1 D i m C o n fi g
Ty p e : < D i m >
L o w Tr i m :
< 0 % >
H i g h Tr i m :
< 1 0 0 % >
P re s e t L e v e l :
< L a s t >
B u r n - i n H o u r s :
< 1 0 0 >
S E N D
P R I O R N E X T
Choose
SEND
Press
Select
To Configure Next Load
Point at Device, Press Select
To Exit , Press HOME
P o i n t t o a n y I R
e n a b l e d d e v i c e o n
t h e n e t w o r k
P r e s s ‘ S e l e c t ’