Button Confi guration
Fade On, Fade Off
Fade On and Fade Off
determines the time that it
takes for loads bound to this
rocker to reach the target
level.
The fade time defaults are
Use Load’s. By default, all
loads carry a two second
ON and OFF fade time. Each
rocker and button can be
set for a different fade time
independently for the same
loads, allowing fast or slow
load fade depending on the button or rocker used.
Fade time value options are from None (immediate)
to 18 hours in duration. As you scroll through the
values, the units of measure change from seconds
to minutes to hours.
Ramp Rate
Ramp Rate determines the
speed (or rate) at which the
light level of bound loads
increases or decreases
when the top or bottom
of the rocker is
pressed and held
. The default
value is 17%/second which means that it takes
approximately 6 seconds to ramp from 0-100%.
Send, Next Button
These selections are described on page 59.
R o c k e r B u t t o n C o n fi g
F a d e O n :
< 4 0 s e c >
F a d e O ff :
< U s e L o a d ’s >
R a m p R a t e :
< 1 7 % / s e c >
S E N D N E X T B U T T O N
R o c k e r B u t t o n C o n fi g
F a d e O n :
< U s e L o a d ’s >
F a d e O ff :
< 5 m i n >
R a m p R a t e :
< 1 7 % / s e c >
S E N D N E X T B U T T O N
Choose <Use Load’s> or
<None up to 18 hours>
Choose <Use Load’s> or
<None up to 18 hours>
R o c k e r B u t t o n C o n fi g
F a d e O n :
< U s e L o a d ’s >
F a d e O ff :
< U s e L o a d ’s >
R a m p R a t e :
< 1 7 % / s e c >
S E N D N E X T B U T T O N