72
Advanced Settings (LMLS-600)
Force Open Loop:
When set to “Yes”,
this parameter causes
the sensor to always
reference the Open-Loop
sensor during control
operations, and use the
Closed-Loop sensor only
for Automatic Calibration
process. For true dual-
loop control, this parameter must be set to “No”.
Available choices: Yes or No
Recomm Thresh
The open-loop light
level below which
the LMLS-600 enters
recommissioning mode.
If this parameter is set
to 0, automatic daily
recommissioning is
disabled.
Range: 0 to 255
D a y l i g h t i n g L M L S - 6 0 0
M a x E L L i g h t :
D a y l i g h t R a t i o :
F o r c e O p e n L o o p :
R e c o m m T h r e s h :
R e c o m m D e l a y :
E n a b D i a g M s g s
N E X T
S E N D
1 . 8 3 3 f c
0 . 0 7 6 2
< Ye s >
< 2 f c >
< 0 m i n >
< A l l >
Press Left/Right arrow
to choose Yes or No
D a y l i g h t i n g L M L S - 6 0 0
M a x E L L i g h t :
D a y l i g h t R a t i o :
F o r c e O p e n L o o p :
R e c o m m T h r e s h :
R e c o m m D e l a y :
E n a b D i a g M s g s
N E X T
S E N D
1 . 8 3 3 f c
0 . 0 7 6 2
< Ye s >
< 1 0 f c >
< 0 m i n >
< A l l >
Press Left/Right arrow
to raise or lower
Recomm Thresh
footcandles