Zone Settings (LMLS-500 Only)
Ramp Up
Determines the speed (or
rate) at which the light level
of bound loads increases.
The default is 20% per
second because the end
user needs light quickly.
Range: 1% per second to 100% per second.
Ramp Down
Determines the speed (or
rate) at which the light level
of bound loads decreases.
The default is 2% per
second because a slow
ramp down will help the
eye adapt to the
new light level.
Range: 1% per second to 100% per second.
Cut Off Delay
The time that the controlled lighting will remain at
a minimum dimmed level, even with high daylight
contribution, before the lights will be switched OFF.
Range: Never to 30 min.
Send
Press the SEND button to save the new settings.
D a y l i g h t i n g L M L S - 5 0 0
S E N D N E X T Z O N E D O N E
S e t p o i n t :
R a m p U p :
R a m p D o w n :
C u t O f f D e l a y :
< 5 0 f c >
< 2 0 % s e c >
< 2 % s e c >
< 1 0 m i n >
Z o n e 1
D i m m e d
D a y l i g h t i n g L M L S - 5 0 0
S E N D N E X T Z O N E D O N E
S e t p o i n t :
R a m p U p :
R a m p D o w n :
C u t O f f D e l a y :
< 5 0 f c >
< 2 0 % s e c >
< 2 % s e c >
< 1 0 m i n >
Z o n e 1
D i m m e d