Adjusting Sensor Parameters
ADJUSTING SENSOR PARAMETERS
Using Current Settings, you can view all parameters
applicable to the type of sensor that is currently
communicating with the LMCT-100. You can modify
settings, send them to the sensor, and/or store them
in the LMCT-100.
Time Delay
Step 1: push
or
to
adjust the value.
Options: <1 to 30 minutes>,
and <Override> to disable
the sensor.
Step 2: push
to activate
the next fi eld.
Detection Sensitivity
S e n s o r C o n fi g
T i m e D e l a y :
< 2 0 m i n >
P I R S e n s :
< 9 0 % >
U S S e n s :
< 7 0 % >
Tr i g g e r :
< P I R O n l y >
R e t r i g g e r : < P I R
O n l y >
Wa l k t h r u : < O ff >
S E N D S AV E R E C E I V E
Adjust PIR
Sensitivity
Adjust
Ultrasonic
Sensitivity
S e n s o r C o n fi g
T i m e D e l a y :
< 2 0 m i n >
P I R S e n s :
< 9 0 % >
U S S e n s :
< 7 0 % >
Tr i g g e r :
< P I R O n l y >
R e t r i g g e r : < P I R
O n l y >
Wa l k t h r u : < O ff >
S E N D S AV E R E C E I V E
Press the
Down Arrow
for Ultrasonic
Step 1: push
or
to adjust the value. PIR and
Ultrasonic sensitivities vary from 0% to 100% in 10%
increments.
Note: Only sensitivity of technology that is present
can be changed.
Step 2: push
to activate the next fi eld.
S e n s o r C o n fi g
T i m e D e l a y :
< 2 0 m i n >
P I R S e n s :
< 9 0 % >
U S S e n s :
< 7 0 % >
Tr i g g e r :
< P I R O n l y >
R e t r i g g e r : < P I R
O n l y >
Wa l k t h r u : < O ff >
S E N D S AV E R E C E I V E
Adjust
Time Delay
Minutes