Zone Settings (LMLS-500 Only)
ZONE SETTINGS (LMLS-500 ONLY)
Zone Settings allows you to modify the photosensor
Daylighting Setpoints, Time Delays and Ramp Rates.
Press
Select
L M L S - 5 0 0 0 2 9 3 7 2 4 9 0 9
Z o n e S e t u p
C a l i b r a t i o n
Z o n e S e t t i n g s
A d v a n c e d S e t t i n g s
Te s t M o d e
Choose
Zone Settings
When Zone Settings is selected, one of two screens
is displayed depending on the Operation Mode of the
Zone (Switched) or (Dimming, Bi-Level or Tri-Level):
Switched, Bi-Level or Tri-Level Dimmed
Switched, Bi-Level, or Tri-Level
ON Setpoint
The target illuminance level
below which the LMLS-500
turns the lights ON.
Range: 5 to 150 fc.
D a y l i g h t i n g L M L S - 5 0 0
Z o n e 1
B i - L e v e l
O N S e t p o i n t :
O F F S e t p o i n t :
O N T i m e D e l a y :
O F F T i m e D e l a y :
< 3 5 f c >
< 5 3 f c >
< 2 0 s e c >
< 1 0 m i n >
S E N D N E X T Z O N E D O N E
D a y l i g h t i n g L M L S - 5 0 0
S E N D N E X T Z O N E D O N E
S e t p o i n t :
R a m p U p :
R a m p D o w n :
C u t O f f D e l a y :
< 5 0 f c >
< 2 0 % s e c >
< 2 % s e c >
< 1 0 m i n >
Z o n e 1
D i m m e d
D a y l i g h t i n g L M L S - 5 0 0
O N S e t p o i n t :
O F F S e t p o i n t :
O N T i m e D e l a y :
O F F T i m e D e l a y :
< 3 5 f c >
< 5 3 f c >
< 2 0 s e c >
< 1 0 m i n >
Press Left/Right arrow
to raise or lower
ON Setpoint footcandles
Z o n e 1
B i - L e v e l
S E N D N E X T Z O N E D O N E