Button Confi guration
Lock Button
Lock Button options are
Yes and No. Selecting Yes
limits the button function to
executing the scene per the
Mode setting; light levels
for the assigned scene can not be recorded from this
scene button. A user can record the scene light level
from this button if Lock Button is No.
Fade On, Fade Off
Fade On and Fade Off
determines how much
time it takes for the loads
to reach their target levels
when this button is pressed.
The fade time defaults are
Use Load’s. By default, all
loads in a scene carry a two
second ON and OFF fade
time. Each button can be
set for different fade times
independently for the same
scene. Application: This
feature allows the user to
recall a scene quickly from
one button, but from another button the scene recall
is much slower and gradual.
Fade time value options are from None (immediate)
to 18 hours in duration. As you scroll through the
values, the units of measure change from seconds
to minutes to hours.
S c e n e B u t t o n C o n fi g
Ty p e : < S c e n e
1 >
M o d e : < R e c a l l
S c e n e >
L o c k B u t t o n
< Ye s >
F a d e O n :
< U s e L o a d ’s >
F a d e O ff :
< U s e L o a d ’s >
S E N D N E X T B U T T O N
Choose <Yes> or <No>
S c e n e B u t t o n C o n fi g
Ty p e : < S c e n e
1 >
M o d e : < R e c a l l
S c e n e >
L o c k B u t t o n
< Ye s >
F a d e O n :
< 2 0 s e c >
F a d e O ff :
< U s e L o a d ’s >
S E N D N E X T B U T T O N
Choose <Use Load’s> or
<None up to 18 hours>
S c e n e B u t t o n C o n fi g
Ty p e : < S c e n e
1 >
M o d e : < R e c a l l
S c e n e >
L o c k B u t t o n
< Ye s >
F a d e O n :
< 2 0 s e c >
F a d e O ff :
< 3 m i n >
S E N D N E X T B U T T O N
Choose <Use Load’s> or
<None up to 18 hours>