Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
98
of
100
Use the RIGHT and BACK keys to move between the pages.
Modbus
address
Read
Write
Code
Meaning
Min
Max
17284 R/W
BN01
BACnet IP enable
OFF
ON
17282 R/W
BN02
Device instance
17283 R/W
BN03
BACnet subnet
0
63
17285 R/W
BN04
BACnet IP port
15766 R/W
BN05
Recall factory values from Eeprom
OFF
ON
17286 R/W
BN06
BBMD IP (first part)
0
255
17287 R/W
BN07
BBMD IP (second part)
0
255
17288 R/W
BN08
BBMD IP (third part)
0
255
17289 R/W
BN09
BBMD IP (fourth part)
0
255
17290 R/W
BN10
BBMD port
17291 R/W
BN11
BBMD tmo
Select the parameters with the UP and DOWN keys. Press OK to edit the parameter.
When the parameter is in edit mode:
•
press the UP key to increase the value;
•
press the DOWN key to decrease the value;
•
press the BACK key to select the left box;
•
press the RIGHT key to select the right box;
•
press the OK key to exit the parameter’s edit mode.
Reboot the controller (switch it off and back on) to set the values.
8.12.13. Menu - Cth
– Condenser Tray Heaters