Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
72
of
100
Ac
CW recovery
accesses the cold water
recovery settings, enabling
commands, set point and
differential.
●
C A U T I O N !
Settings should be adjusted by taking into account the configuration of the
system, the use for which the unit is designed, and the unit’s operating limits.
Entering parameters outside the operating limits could lead to malfunction of and/or
serious damage to the unit.
8.9.7. MENU - AA SET POINT
On the A.Settings menu, with the a.SET POINT menu selected, press the RIGHT key to access
the hot water set point setting screen.
Press OK to access the set point editing window. In this window:
1. press the UP key to increase the value by 0.1°C;
2. long press the UP key to increase the value by 2.5°C;
3. press the DOWN key to reduce the value by 0.1°C;
4. long press the DOWN key to reduce the value by 2.5°C;
5. press the BACK key to close set point screen without confirming changes;
6. press the OK key to confirm changes and close the set point screen.
Modbus
address
Read
Write
Code
Meaning
Min
Max
Unit of measurement
16433
RW
ST01
Hot water set point
setting
60°C
90°C
°C
8.9.8. MENU - Ab DOUBLE PROBE
On the A.Settings menu, with the b.DOUBLE PROBE menu selected, press the RIGHT key to
access the double probe function setting screen.
Select the following parameters with the UP and DOWN keys: