Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
99
of
100
On the service menu, with the CTH key selected, press the OK key to access the screen used
to set the Condenser tray heaters parameters.
Modbus
Address
Read Write Code
Meaning
Min
Max
17363
R/W
CTH01 Enable condenser tray heaters OFF
ON
17364
R/W
CTH02
Activation temperature set
point
0.0
20.0
17365
R/W
CTH03 Temperature differential band 0.0
5.0
8.12.14. MENU
– SHC – Secondary hydraulic circuit
On the service menu, with the CTH key selected, press the OK key to access the screen used
to set the secondary (domestic hot water) circuit parameters.
Modbus
address
Read Write Code
Meaning
Min
Max
17292
R/W
SP01 Enable secondary pump
OFF
ON
17293
R/W
SP02 Activation temperature setpoint
0.0
100.0
17294
R/W
SP03 Secondary pump initial speed
0.0
100.0
17295
R/W
SP04 Secondary pump minimum speed
0.0
100.0
17296
R/W
SP05 Secondary pump maximum speed
0.0
100.0
17297
R/W
SP06 Continuous secondary pump
regulation (also with unit OFF)
OFF
ON
17367
R/W
SP07 Enable BT3 alarm
OFF
ON