Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
77
of
100
function” temp
8344
AI9
HP
Refrigerant high
pressure
●
●
●
Bar
8345
AI10 LP
Refrigerant low pressure
●
●
●
Bar
8346
AI11 Oil
Oil temp
●
●
●
°C
8347
AI12 Disch
Compressor discharge
temp
●
●
●
°C
9629
ExAI1 RW in
Source cold water inlet
●
°C
9630
ExAI2 RW out
Source cold water outlet
●
°C
9636
ExAI3 BT3
Secondary circ. water
temp.
●
●
●
°C
9666
ExAI4 Subcool
Evaporator outlet temp
(Only with secondary
pump)
●
●
●
°C
8.9.12. MENU - Bb Analog Inputs
Modbus
address Code Description Meaning
A/W
A/W with
CW
recovery
W/W Unit of
measurement
8448
AO1
Pmp sp
Utility water pump speed
%
●
●
●
%
8449
AO2
Val op
Thermostatic valve
opening %
●
●
●
%
8450
AO3
Fan sp
Fan speed %
●
●
%
8451
AO4
--
Not used
●
●
●
%
8452
AO5
--
Not used
●
●
●
%
8453
AO6
--
Not used
●
●
●
%
9887
ExAO1 2Pmp sp
Secondary pump
modulation
●
●
●
%
8.9.13. MENU - Bc Digital Inputs
Modbus
address Code Description Meaning
A/W
A/W with CW
recovery
W/W