On the main menu, with the B.I/O VALUES menu selected, press the RIGHT key to access
the sub-menu where more screens can be selected with the UP and DOWN keys.
Index
Menu
Action
A/W
A/W with
CW
recovery
W/W
Ba
Analog IN
displays the analog inputs
●
●
●
Bb
Analog OUT
displays the analog outputs
●
●
●
Bc
Digital IN
displays the digital inputs
●
●
●
Bd
Digital OUT
displays the digital outputs
●
●
●
Access the selected menu with the RIGHT key to view the pages displaying the various IO.
When accessing via Modbus the values are all read-only.
8.9.11. MENU - Ba Analog Inputs
Modbus
address
Code Description
Meaning
A/W
A/W with
CW
recovery
W/W Unit of
measurement
8336
AI1
HW in
Utility hot water inlet
●
●
●
°C
8337
AI2
HW out
Utility hot water outlet
●
●
●
°C
8338
AI3
GC
Refrigerant temp after
gas cooler
●
●
●
°C
8339
AI4
Suct
Refrigerant temp in
suction
●
●
●
°C
8340
AI5
AExt
External air temp
●
●
°C
8340
AI5
SW in
Source water inlet temp
●
°C
8341
AI6
Coil
Coil pack temp
●
●
°C
8341
AI6
SW out
Source water outlet temp
●
°C
8342
AI7
BT1
BT1 “Double probe
function” temp
●
●
●
°C
8343
AI8
BT2
BT2 “Double probe
●
●
●
°C