Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
96
of
100
•
Press the OK key to confirm forcing the defrost cycle;
•
press the BACK key to close the window without confirming selection for forcing the
defrost cycle.
8.12.10. Menu - Cr Cold Recovery
On the service menu, with the CR key selected, press the OK key to access the screen used to
set the cold recovery parameters. Select the parameters with the UP and DOWN keys. Once
the parameter has been selected, press the OK key to edit the parameter. Parameters CR01,
CR02, CR03 are used to enable the function, set the working set point and its differential.
Modbus
address
Read
Write
Code
Meaning
Min
Max
Unit of
measuremen
t
9638
RW
CR01
Enable cold water recovery
OFF
ON
16807 RW
CR02
Cold water recovery set point -30
50
°C
16808 RW
CR03
Cold water recovery
differential
0
30
°C
16518
RW
CR07
High recovery water
temperature
difference warning set point
0
30
°C
16519
RW
CR08
Low recovery water
temperature
difference warning set point
-10
10
°C
16520
RW
CR09
Low recovery water
temperature
difference warning
differential
0
30
°C
16827
RW
CR10
High/low recovery water
temperature difference from
compressor start-up warning
delay
0
1,200
sec
Parameters CR07, CR08, CR09 are used to set the warnings that indicate if the difference
between water inlet and outlet on the recovery heat exchanger is within certain limits. Parameter
CR10 defines the warning delay from compressor start-up.
8.12.11. Menu - Sw Source Water
On the service menu, with the SW key selected, press the OK key to access the screen used to
set the water source parameters.
Select the parameters with the UP and DOWN keys. Once the parameter has been selected,
press the OK key to edit the parameter.