Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
90
of
100
8.12. Cold Side Anti-Freeze (Recovery/Source)
The cold side anti-freeze is managed by parameters AI09-AI16. The reference probe for
operation of the anti- freeze heater and the anti-freeze alarm is the cold recovery heat
exchanger water / source water outlet probe. Parameters AI09 and AI10 control activation of the
cold water side anti-freeze heater on the outlet probe reading. If the water outlet probe is in
alarm, the anti-freeze heater is adjusted by parameters AI11 and AI12 on the inlet probe
reading.
Parameters AI13 and AI14 regulate activation of the cold water side anti-freeze alarm on the
outlet probe reading. If the water outlet probe is in alarm, the anti-freeze alarm is adjusted by
parameters AI15 and AI16 on the inlet probe reading.
8.12.4. MENU - MD RS485 -1 Config
On the service menu, with the MD key selected, press the OK key to access the screen used to
set the RS485-1 serial port. The Modbus/RTU and the BACnet MS/TP protocols are available.
Modbus
address
Read
Write
Code
Meaning
Min
Max
Correspondence