Lync AEGIS Controller
4: APPENDIX A - INTERNAL CONTROL SPECIFICATIONS & TECHNICAL DATA
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
50
of
100
Power supply
24 Vac 50-60 Hz / 20-38V DC not isolated
Absorbed power
35 VA / 15W
Insulation class
2
Operating temperature
-4 ..149°F [-20..65°C]
Storage temperature
-22 .. 158°F [-30..70°C]
Relative humidity
5..95% (without condensation)
I M P O R T A N T
Before starting the unit, some of the connections must be made by the installer
The terminal block for the unit contains some terminals for remote connections. The reference
terminal block is indicated on the wiring diagram with X2. See the following chapters for detailed
descriptions of their Meanings/use.
DIGITAL INPUTS
Type of
connection by
the installer
Terminal
numbers
Voltage on
the
terminals
Meaning
A/W
A/W with
CW
recovery
W/W
Dry contact
digital input
1
– 2
24 Vac
Digital input for
switching the unit ON
and OFF.
●
●
●
Dry contact
digital input
24
– 8
24 Vac
Digital input for utility
Hot Water request.
●
●
●
Dry contact
digital input
24
– 5
24 Vac
Digital input for Cold
Water recovery
request.
●
Dry contact
digital input
24
– 71 24 Vac
Digital input for the
secondary hydraulic
circuit water pump
circuit breaker
●
●
●
DIGITAL OUTPUTS
Type of
connection by
the installer
Terminal
numbers
Voltage
on the
terminals
Meaning
A/W
A/W
with CW
recovery
W/W