exchanger and the storage tanks. Installation of BT1, BT2, and BT3 probes must be done by
the installer prior to operation.
Note that the tanks must be hydraulically connected in series as shown below, not in
parallel.
When the temperature probe BT1 reaches the value "Set point unit ON", (set point (ST03) minus
differential (ST04)), the unit will be turned on. The unit will continue to heat the water to the
set temperature as long as the temperature BT1 remains below the
“Set point unit OFF” value
(ST03). Once BT1 reaches "Set point unit OFF" the unit will be turned off.
To limit the possible discomfort that can be generated by excessive heat dissipation the
probe BT2 may be used to operate a "comfort" function. In this case, even if the temperature
BT1 is higher than the value of "Set point unit OFF", the unit operate when the BT2 is lower than
a value of "Set point comfort ON".
Operation with only the BT1 probe is allowed, while the use of the BT2 probe requires the
presence of the BT1 probe. The unit will turn off only when both the BT1 and BT2 temperatures
are greater than the related set points.
BT3 probe
– secondary
side pump modulation
Set Point ON
comfort
Set Point OFF
comfort