Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
Integrating the Control Unit into the LON
Service
A
B
C
D
E
Multiple boiler system
Set coding “01:2” in
the “Boiler” group.
Multiple boiler system
Set coding “01:2” in
the “Boiler” group
Multiple boiler system
Set coding “01:2” in
the “Boiler” group.
--
--
Boiler number 1
Coding “07:1” in the
“Boiler” group
Boiler number 2
Set coding “07:2” in
the “Boiler” group.
Boiler number 3
Set coding “07:3” in
the “Boiler” group
--
--
Number of connected
boilers. Set coding
“35:1” to “35:8” in the
“Cascade” group.
--
--
--
--
Participant No. 1.
Coding “77:1” in the
“General” group.
Participant No. 2.
Coding “77:2” in
the “General” group.
Participant No. 3.
Set coding “77:3” in
the “General” group.
Participant No. 99.
Participant No. 10.
Coding “77:10” in the
“General” group.
Control unit is fault
manager.
Coding “79:1” in the
“General” group.
Control unit is not fault
manager.
Coding “79:0” in the
“General” group.
Control unit is not fault
manager.
Coding “79:0” in the
“General” group.
Appliance is fault
manager.
Control unit is not fault
manager.
Coding “79:0” in the
“General” group.
Control unit transmits
time.
Coding “7b:1” in the
“General” group.
--
--
Appliance receives
time.
Control unit receives time.
Set coding “81:3” in the
“General” group.
Control unit transmits
outdoor temperature.
Coding “97:2” in the
“General” group.
--
--
--
Control unit receives
outdoor temperature.
Set coding „97:1“ in
the “General” group.
Viessmann system
number, coding “98:1”
in the “General” group.
Viessmann system
number, coding “98:1”
in the “General” group.
Viessmann system
number, coding “98:1”
in the “General” group.
--
Viessmann system
number, coding “98:1”
in the “General” group.
LON Participant fault
monitoring
Coding “9C:20” in the
“General” group.
LON Participant fault
monitoring
Coding “9C:20” in the
“General” group.
LON Participant fault
monitoring
Coding “9C:20” in the
“General” group.
--
LON Participant fault
monitoring
Coding “9C:20” in
the “General” group.
Remove terminal end resistor on
A
to carry on LON
connection
The LON communication module is factory installed.
Vitotronic 200-H:
The LON communication module (accessory) must be
plugged in.
Refer to the Vitotronic 200-H Installation and
Service Instructions.
The same participant number may
not
be assigned twice
within a LON.
Example for a multiple-boiler system:
Within a LON, the system numbers (Coding “98” in the
“General” group) must be the same.
Only one control unit may be encoded as fault manager.
The data transfer via LON can take up to several
minutes.
Legend
A
Boiler section 1/ lead control unit
B
Boiler section 2/ lag control unit 1
C
Boiler section 3/ lag control unit 2 (CA3 5.0 and 6.0 only)
D
Vitocom 100 LAN 1 with integrate LON terminal end
resistor
E
External control unit (Vitotronic 200-H HK1B)
Note:
Cascade combination of CA3 boilers cannot exceed
8 boiler sections.
Vitotronic 300 GW6C for CA3 2.5, 3.0, 3.5 and 4.0
Vitotronic 300 GW6C for CA3 5.0 and 6.0