Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
Electrical Connections
(continued)
Installation
DIN rail X0 Power supply connection
CA3 2.5, 3.0, 3.5 and 4.0
120 VAC/60 Hz/1 phase
(20 Amps - full load amperage)
240 VAC/60 Hz/1 phase
(20 Amps - full load amperage)
208 Y/120VAC-60Hz - 3 phase
(20 Amps - full load amperage)
(4 wire L1, L2, L3, N, G)
DIN rail X0 Power supply connection
CA3 5.0 and 6.0
Legend
1
Factory installed terminal bridge
2
Terminal bridge must be removed on site for 240VAC
connection.
WARNING
Incorrectly executed electrical installations can lead to
injuries from electrical current and result in appliance
damage.
WARNING
The control must be grounded.
Ensure that ‘L’, ‘N’ and ‘G’ are not interchanged.
DIN rail X0 Power supply connection (optional)
CA3 2.5, 3.0, 3.5 and 4.0
IMPORTANT
Electrical installations must comply with the latest edition of:
In the U.S.A., the National Electrical Code (NEC),
ANSI/NFPA 70 and any other state, local codes and/or
regulations.
In Canada, the Canadian Electrical Code (CEC),
CSA C22.1 Part 1 and any other province, territory,
local codes and/or regulations.