43
5790 733 - 07
Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
Vitocom 100, LAN 1 Display and Control Elements
With cover
“T1”
Maintenance button (see page 42)
“3”
IP connection status (green and yellow LED)
“4”
Operating status display (green and red LED)
LON service indicator “1”
Flashes green
LON participant check successful (see page 87).
IP State of connection “3”
Flashes yellow/illuminates yellow Establishing a connection (see page 86), or connection fault (see page 47),
to the DSL router (DHCP server), internet or vitodata server.
Illuminates green
Connection to the Vitodata server established.
Flashes green
Data transfer between the Vitocom 100 and Vitodata server enabled.
Operating status display “4”
Illuminates red
Enabling maintenance (see page 46).
Flashes red
Heating system fault.
Flashes green longer than 3 min
Fault when initializing the Vitocom 100 (see page 47).
Illuminates green
“Standard mode”, no heating system or Vitocom 100 fault.
Flashes green
The Vitocom 100 will initialize after the power supply unit is lugged in or the reset
button is pressed.
Flashes green quickly
Software update is being installed. The device must
not
be isolated from the mains.
Explanation of displays
Switching on the Vitocom 100, LAN 1
Initialization
When the Vitocom 100 is initializing, the following
processes run in sequence:
1. The Vitocom 100 starts and loads the internal
operating software.
The operating status display “4” flashes green after
max. 40 sec. After a few minutes, operating status
display “4” illuminates green.
2. Connect with the Vitodata server
IP connection status display “3” shows
the procedure for establishing the connection:
H
Flashes yellow slowly:
H
The Vitocom 100 is integrated into the on-site IP
network (obtain IP address of DHCP server).
H
Flashes yellow quickly:
H
Internet connection is being established.
H
Illuminates yellow:
H
Connection to the Vitodata server is being established.
H
Illuminates green:
H
Secure connection to the Vitodata server is established.
Initialization successful
The Vitocom 100 is ready for operation. The following
LED indicators illuminate green: operating status display
“4” and IP connection status “3”.
Initialization not successful
If a fault occurs during initialization, this is indicated
by the associated LED indicators. For troubleshooting
measures, see page 47.
Installation