Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
Coding Level 1
“General” Group
(continued)
Coding in the factory set condition
Possible change
“Automatic summer/wintertime changeover”
81:1
Automatic summer/wintertime changeover.
81:0
Manual summer/wintertime changeover
81:2
Do not adjust!
81:3
With LON communication module:
The control unit receives the time.
“Summer time starts: Month”
82:3
March
82:1
to
82:12
January to December
“Summer time starts: Week of the selected month”
83:2
Week 2 of the selected month.
83:1
to
83:5
Week 1 to week 5 of the selected month.
83:6
Last week - 1 week
83:7
Last week - 2 weeks
83:8
Last week - 3 weeks
83:9
Last week - 4 weeks
83:10
to
83:14
Special function
“Summer time starts: Day of the selected week”
84:7
Last Sunday of the selected month.
84:1
to
84:7
Monday to Sunday.
“Wintertime starts: Month”
85:11
November
85:1
to
85:12
January to December
“Wintertime starts: Week of the selected month”
86:1
Week 1 of the selected month.
86:1
to
86:5
Week 1 to week 5 of the selected month.
“Wintertime starts: Day of the selected week”
87:7
Last Sunday of the selected month.
87:1
to
87:7
Monday to Sunday
“Operation enabled/blocked”
8f:0
Do not adjust!
--
--
“Set supply temperature for external demand”
9b:70
Set to 158°F (70°C)
9b:0
to
9b:127
Adjustable from 32°F to 261°F (0°C to 127°C)
(limited by boiler specific coding).