103
5790 733 - 07
Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
1. Close the gas shut-off valve.
2. Switch OFF the main circuit breaker or the power supply
and safeguard against unauthorized reconnection.
3. Remove the boiler left side panels (see page 88).
4. Disconnect power cable with plug
fÖ
. Then
disconnect the burner cables with plugs
§
A/
§
B,
aG
A/
aG
B,
fA
,
gD
,
lÖ
and in addition to plug
avG
from the burner control unit and pull out of the burner
casing.
Service
Burner Interface Panel
WARNING
Mains voltage can be extremely dangerous.
For maintenance work, isolate the system from the
power supply.
CA3 3.5 to 6.0
CA3 2.5 and 3.0