Selecting external analogue input
Available if
"No"
was selected for the cascade.
Press the following buttons:
1.
|
/
~
for external default output with external ana-
logue input
"Yes/No"
.
2.
d
to confirm.
Setting the number of buffer temperature sensors
Available if
"No"
was selected for the cascade.
Press the following keys:
1.
|
/
~
for heating water buffer cylinder temperature
sensor
"No"
,
"3"
,
"4"
or
"5"
.
The number of connected sensors is auto-
matically recognised and preset.
2.
d
to confirm.
Selecting the type of heating water buffer cylinder
Available if the following settings were previously
selected:
■
Buffer temperature sensor
"3"
,
"4"
or
"5"
and
■
Cascade
"No"
.
To change the point for capturing the system tempera-
ture from the top or 1st temperature sensor to the
2nd temperature sensor in the heating water buffer cyl-
inder, select buffer type 1:
1.
|
/
~
for buffer type.
2.
d
to confirm.
Setting the heating water buffer cylinder minimum temperature (top)
Available if
"1"
was selected for the buffer type.
Press the following buttons:
1.
|
/
~
for setting the minimum temperature of the top or
first temperature sensor of the heating water buffer cylinder.
2.
d
to confirm.
Setting buffer charging up to buffer temperature sensor
Available if the number of buffer temperature sensors
selected was
>
0.
Press the following buttons:
1.
|
/
~
Heating water buffer cylinder charging up to
the temperature sensor of the heating water
buffer cylinder
"1"
,
"2"
,
"3"
,
"4"
or
"5"
.
2.
d
to confirm.
Commissioning, inspection, maintenance
Commissioning the heating system
(cont.)