97
Coding in the delivered condition
Possible change
Discharge delay
32:5
Delay of 5 seconds
32:0
to
32:300
Setting range in seconds
External charging cycle - ON
40:5
External charging cycle of
5 seconds
40:2
to
40:250
Setting range in seconds
External charging cycle - OFF
41:0
External charging cycle of
0 seconds
41:0
to
41:1000
Setting range in seconds
External charging delay
42:5
Delay to external charging
5 seconds
42:0
to
42:300
Setting range in seconds
Discharge, reversing interval
BD:...
Interval: Discharge system
changes direction of rotation
BD:0
to
BD:300
Setting range in seconds
Discharge, preferred direction
BE:...
Preferred direction of discharge
BE:0
to
BE:1
0 = No
1 = Yes
Delay, hydraulic drive unit
C1:...
Delay to hydraulic drive unit
C1:0
to
C1:300
Setting range in seconds
Transverse screw conveyor, emergency mode delay
C2:...
Emergency mode delay of the
transverse screw conveyor
C2:0
to
C2:1000
Setting range in seconds
Hydraulic drive unit, emergency mode
C3:2
Emergency mode delay of the hy-
draulic drive unit
C3:0
to
C3:250
Setting range in seconds
Buffer
Coding
Coding in the delivered condition
Possible change
Maximum set temperature, buffer cylinder
34:85
Max. average temperature of the
heating water buffer cylinder, 85 °C
(upper limit of control range)
34:30
to
34:100
Setting range in °C
Minimum set temperature, buffer cylinder
35:60
Min. set temperature of the heating
water buffer cylinder, 60 °C (lower
limit of control range)
35:30
to
35:100
Setting range in °C
Codes
Code 1
(cont.)
5679249
Codes