107
Coding in the delivered condition
Possible change
Transfer heat
44:100
Heat is transferred from the coded
heating circuits, starting at a boiler
water temperature of 100 °C.
44:70
to
44:120
Setting range in °C
Material controller
46:...
Speed of boiler material controller
46:1
to
46:30
A small value slows the controller
down, a large value speeds it up.
Output controller
47:...
Speed of boiler output controller
47:1
to
47:30
A small value slows the controller
down, a large value speeds it up.
Boiler water temperature delay
49:60
Shutdown delay of 60 seconds if
the max. flow temperature of the
boiler is exceeded
49:0
to
49:240
Setting range in seconds
Material controller, delay
4A:...
Delay of fuel delivery in seconds
on fuel ignition
4A:1
to
4A:420
Setting range in seconds
Light barrier, firebed cycle ramp
52:...
Cycle ramp setting for the feed
screw conveyor when firebed light
barrier is interrupted in seconds
52:1
to
52:50
Setting range in seconds
Material controller, flue gas fan
55:...
Factor for varying fan speed
55:0
to
55:50
Setting range without unit
Material controller, minimum limit
56:...
Min. air damper position in % at
partial load
56:1
to
56:190
Setting range in %
O2 control active
5F:0
Control via flue gas oxygen con-
tent
not
active
5F:1
Control via flue gas oxygen content
active
5F:2
Cannot be adjusted
Status message in the case of a
fault.
Flow controller active
60:1
Control of flow active
60:0
Control of flow
not
active
60:2
Flow control via boiler circuit pump
Only possible for boiler circuit
pumps with PWM signal.
Codes
Code 2
(cont.)
5679249
Codes