50
Press the following buttons:
1.
|
/
~
for the required supply system
"0"
,
"1"
,
"2"
, ...,
"13"
.
2.
d
to confirm.
When configuring the supply system, you can choose
from the following:
Charging
scheme
Function
Outputs
Inputs
0
External charging
222
241, 246
1
Flexible agitator discharge
218
240, 241, 244
2
Screw conveyor, external charging
216, 222
236, 239, 241, 243, 246
3
Screw conveyor, flexible agitator dis-
charge
216, 218
236, 239, 240, 241, 243,
244
4
AH discharge (screw conveyor, agitator)
216, 218
236, 239, 240, 241, 243,
244
6
Rotary lock valve, vacuum module
214, 216
241, 243, 245, 248
7
Rotary lock valve, vacuum module, au-
tom. changeover unit
214, 215, 216
241, 243, 245, 248, 250
8
Rotary lock valve, vacuum module, ex-
ternal charging
214, 216, 222
241, 243, 245, 246, 248,
251
9
Rotary lock valve, vacuum module, dis-
charge screw conveyor
214, 216, 218
240, 241, 243, 244, 245,
248, 251
10
Rotary lock valve, vacuum module, mole 214, 215, 216
241, 243, 245, 248, 251
11
Rotary lock valve, vacuum module, ex-
traction screw conveyor
214, 215, 216
241, 243, 245, 248, 251
12
External charging control panel
with
hydraulics, transverse screw conveyor
and screw conveyor
222
246, CAN
13
External charging control panel
with
rotary lock valve and pendulum dis-
charge AP including reversal of rotational
direction
222
246, CAN
Setting the charging scheme
Depending on the system equipment level, the coding
address has to be adjusted.
The available codes depend on the selected charging
scheme. Subject to the selected value, the corre-
sponding coding addresses are available.
Note
Motors may only be connected if they have internal
motor protection (Klixon).
A separate input is provided for motor protection.
Commissioning, inspection, maintenance
Commissioning the heating system
(cont.)
5679249