98
Coding in the delivered condition
Possible change
Buffer cylinder charging to sensor
36:3
The boiler charges the heating wa-
ter buffer cylinder up to buffer tem-
perature sensor
3
.
36:1
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor
1
(top).
36:2
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor
2
.
36:4
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor
4
.
36:5
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor
5
.
Buffer cylinder charging up to temperature
37:60
The boiler charges the heating wa-
ter buffer cylinder until the temper-
ature of 60 °C is reached at the se-
lected sensor (code
"36:1-5"
, buf-
fer cylinder group).
37:30
to
37:100
Setting range in °C
Boiler start, sensor
39:1
If the set system temperature at
the
1st
buffer temperature sensor
is undershot, the boiler starts.
39:2
If the set system temperature at the
2nd
buffer temperature sensor (top)
is undershot, the boiler starts.
39:3
If the set system temperature at the
3rd
buffer temperature sensor is un-
dershot, the boiler starts.
39:4
If the set system temperature at the
4th
buffer temperature sensor is un-
dershot, the boiler starts.
39:5
If the set system temperature at the
5th
buffer temperature sensor is un-
dershot, the boiler starts.
Additional heat generator
Available if code
"Additional boiler"
is set to
"Yes"
.
For code
"Additional boiler"
, see Hardware group.
Codes
Code 1
(cont.)
5679249
Codes