96
Coding in the delivered condition
Possible change
Light barrier delay screw conveyor
0F:5
Delay of 0.5 seconds
0F:0
to
0F:100
Setting range in tenths of seconds
Feed screw conveyor heat-up cycle
14:...
Start cycle of the feed screw con-
veyor in % after boiler ignition
14:1
to
14:100
Setting range in %
Feed screw conveyor maximum cycle
15:...
Max. cycle limit of feed screw con-
veyor in %
15:1
to
15:100
Setting range in %
Vacuum module cycle - ON
28:20
Cycle of 20 seconds
28:2
to
28:600
Setting range in seconds
Vacuum module cycle - OFF
29:10
Cycle of 10 seconds
29:0
to
29:250
Setting range in seconds
Vacuum module pre-flushing time
2A:10
Pre-flushing time of 10 seconds
2A:0
to
2A:60
Setting range in seconds
Vacuum module post-flushing time
2B:10
Post-flushing time of 10 seconds
2B:0
to
2B:60
Setting range in seconds
Day hopper idle runtime
2C:15
Idle runtime, 15 min
2C:1
to
2C:600
Setting range in min
Screw conveyor delay
2E:2
Delay of 2 seconds
2E:0
to
2E:100
Setting range in seconds
Light barrier delay transfer discharge
2F:5
Delay of 5 seconds
2F:0
to
2F:300
Setting range in seconds
Discharge cycle - ON
30:5
Discharge cycle of 5 seconds
30:2
to
30:250
Setting range in seconds
Discharge cycle - OFF
31:0
Discharge cycle of 0 seconds
31:0
to
31:1000
Setting range in seconds
Codes
Code 1
(cont.)
5679249
Codes