99
Coding
Coding in the delivered condition
Possible change
Buffer charging until sensor
D0:1
The additional heat generator
charges the heating water buffer
cylinder up to buffer temperature
sensor 1.
Note
Only useful if the additional heat
generator has its own boiler circuit
pump.
D0:0
The heating water temperatures of
the heating water buffer cylinder
temperatures are ignored.
Note
If buffer cylinder control valve instal-
led, no buffer charging.
D0:2
The additional heat generator charg-
es the heating water buffer cylinder
up to buffer temperature sensor
2
.
D0:3
The additional heat generator charg-
es the heating water buffer cylinder
up to buffer temperature sensor
3
.
D0:4
The additional heat generator charg-
es the heating water buffer cylinder
up to buffer temperature sensor
4
.
D0:5
The additional heat generator charg-
es the heating water buffer cylinder
up to buffer temperature sensor
5
.
Buffer charging until temp.
D1:75
The additional heat generator
charges the heating water buffer
cylinder until the temperature of
75 °C at the selected sensor (code
"D0:1-5"
) is reached.
D1:50
to
D1:100
Adjustable value in °C
Start delay
D2:10
Start delay of the additional heat
generator
D2:0
to
D2:250
Adjustable value in minutes
Start temperature set system temperature
D3:-10
Start temperature of the additional
heat generator
Condition for starting:
Actual system temperature < set
system temperature minus selec-
ted value (here: 10 K)
D3:-100
to
D3:-1
Adjustable value in K
Minimum runtime
D4:5
Minimum runtime of the additional
heat generator
D4:0
to
D4:250
Adjustable value in minutes
Min pause duration
D5:5
Minimum pause time of the addi-
tional heat generator
D5:0
to
D5:250
Adjustable value in minutes
Codes
Code 1
(cont.)
5679249
Codes