124
Displayed fault
code
System characteristics
Cause
Measures
B0
Burner locked out
Fault, light barrier, feed
screw conveyor
Clean light barrier
B1
Burner locked out
Shut-off gate valve stick-
ing
Check shut-off gate valve for ease
of operation
B2
Burner locked out
Fault, light barrier, screw
conveyor
Clean screw conveyor light barrier
B3
Burner locked out
Fault, external charging
Check whether external charging is
working
B4
Control mode
Fuel store empty
Check fuel store fill level
B5
Burner locked out
Fault, motor, feed screw
conveyor
Check feed screw conveyor motor
B6
Burner locked out
Fault, motor, screw con-
veyor
Check screw conveyor motor
B7
Burner locked out
Fault, motor, ash removal
Check ash removal motor
B8
Burner locked out
Fault, suction turbine mo-
tor
Check suction turbine motor
B9
Burner locked out
Fault, feed screw convey-
or reversal
Check feed screw conveyor rever-
sal
BA
Burner locked out
Maintenance cover of feed
screw conveyor open
Check maintenance cover of feed
screw conveyor
BB
Burner locked out
Maintenance cover of
screw conveyor open
Check maintenance cover of screw
conveyor
BC
Burner locked out
Maintenance cover of dis-
charge open
Check maintenance cover of dis-
charge
BD
Burner locked out
Maintenance cover/door
of fuel store open
Check maintenance cover/door of
fuel store
BE
Burner locked out
Proximity switch at dis-
charge screw conveyor is
permanently active
Clean sensor if possible
BF
Burner locked out
Rotary lock valve motor is
too hot
Check rotary lock valve motor for
ease of operation and acknowl-
edge fault
C8
Burner locked out
Changeover unit has not
reached position
Checking the changeover unit
C9
No fuel transport
Vacuum module spends
too long in constant oper-
ation
■
Check suction lines for block-
ages and remove if necessary
■
Ensure there is sufficient fuel in
the fuel store
D0
Warning
Ash box full
■
Emptying the ash box
■
Confirm message "Has the ash
box been emptied?"
D1
Warning
Day hopper empty
■
Fuel check
■
Check supply times
■
Check vacuum module
D2
Warning for log boiler
Too little heat available for
consumers
Recharge wood
D3
Warning for log boiler
Too little heat available for
consumers
Heat up the log boiler
D4
Warning
The boiler is dirty
Clean the boiler
D5
Warning
Boiler maintenance nec-
essary
Carry out boiler maintenance
Troubleshooting
Fault codes
(cont.)
5679249
Diagnosis