42 Chapter 3 Web Page Of RDU-A G2
RDU-A G2 Intelligent Monitoring Unit User Manual
Figure 3-44 Example 1 for alarm linkage
Example 2:
If it is required that when the front door or back door of the rack is open, the alarm lamp turns on. Suppose that the
DI1 and DI2 ports of the RDU-A G2 are respectively connected with the door status sensors on the front and back
door, and the alarm lamp is mounted on the DO1 port. You can achieve the alarm linkage function through the
following configuration:
Expression: [RDU-A DI1 Alarm] OR [RDU-A DI2 Alarm] = [RDU-A DO1] [Close]
The configuration method is shown in Figure 3-45. When the alarm signal of RDU-A G2 DI1 Open or RDU-A G2 DI2
Open generates an alarm, RDU-A G2 DO1 will close, thus the alarm lamp turns on.
Figure 3-45 Example 2 for alarm linkage
3.4.5 Data & History
The
Data & History
menu supplies query service of all types of historical data and logs for the user.
On the RDU-A G2 homepage, click
Data & History
in the left part, four submenus appear, including:
Device
Information
,
History Data
,
History Log
and
Clear History
.
Device Information
Click the
Device Information
submenu under the
Data & History
menu, the page shown in Figure 3-46 pops up.
The page includes two tabs:
Device Information List
and
Export SNMP MIB
.
1. Device Information List
As shown in Figure 3-46, the page lists the main information of all equipment. Click the
Download
button to
download the query result.