28 Chapter 3 Web Page Of RDU-A G2
RDU-A G2 Intelligent Monitoring Unit User Manual
Figure 3-29 Teamwork parameters setting page (authorized version)
As for the AC Teamwork function of RDU-A G2 standard version, the descriptions are as follows:
The AC Teamwork function only supports one AC team,
[1]TMW
by default, without adding and deleting functions;
meanwhile, the team name cannot be changed. However, the authorized version does not have such limit.
Click the
Click here to add teamwork
link in the
AC Teamwork
list, you can add a new AC team. After the team
parameters are configured, click the Add button to save the setting, at this time, the new-added team will be
displayed in the left
AC Teamwork
list.
For detailed parameter descriptions of the teamwork parameters setting page, see Table 3-1.
Add, edit or delete AC in the team on the AC parameters setting page, refer to
2. AC Parameters
in this section;
Select the AC team which needs to be edited in the
AC Teamwork
list. Similar to the adding team procedures, edit
the team parameters on the teamwork parameters setting page, and set the AC parameters in the team on the AC
parameters setting page. After editing, click the
Modify
button (see Figure 4-20) to save the setting;
Select the AC team which needs to be deleted in the
AC Teamwork
list, and click the
Delete
button to save the
setting.
Table 3-1 Parameters on the teamwork parameters setting page
Team parameters
Default
Low limit
Upper limit
Notes
Standard
version
Authorized
version
Teamwork Mode
Single-alone
Single-alone
(0)
Teamwork (1)
Single-alone (0):
Each AC in the team
operates separately;
Teamwork (1): Each
AC in the team
participates in team
Boolean calculation
√
√
AC minimum count
1
1
AC number
in the team
/
√
AC minimum run
time
30
5
180
Unit: min
√
Return air
temperature
20
15
30
Unit: °C
√
√
Deviation of return
air temperature
5
1
5
Unit: °C
√
√