OPERATORS MANUAL
ORION II
Orion II 500-10000 Operators
Page 75 of 95
Manual Part no: DOMAON0100 Issue A
April 2008
6.8.3 Additional Option 11 (TTS) Alarms
Alarm
Description
Warning - Low Flow - TTS Pump -
FT1102
This warning is generated if the flow has remained
outside the allowable band for a time.
Warning - High Flow - TTS Pump -
FT1102
See above
Fatal - PU11-01 Pump Not
Stopped
The pump has been stopped but the digital input to
say its running has remained on.
Fatal - PU11-01 Pump Not Started
The pump has been started but the digital input to
say its running has not come on.
Warning - Softener 1 - Service
Position Lost
While the softeners is in service the service position
has been lost.
Warning - Softener 2 - Service
Position Lost
While the softeners is in service the service position
has been lost.
Warning - Softener 1 Still Hard
after Regen
The softeners is still hard after a regeneration
process.
Warning - Softener 2 Still Hard
after Regen
The softeners is still hard after a regeneration
process.
Fatal - Shutdown -Softener 2
Hardness Switch
While in service softeners 2 has gone hard. The unit
is shut down.
Warning - Analogue Input TT1101
Out of Range
This analogue input has remained out of range for
30 seconds. It is either less than 3.75 mA or greater
than 20.25 mA
Warning - Analogue Input FT1102
Out of Range
See above