OPERATORS MANUAL
ORION II
Orion II 500-10000 Operators
Page 73 of 95
Manual Part no: DOMAON0100 Issue A
April 2008
Alarm
Description
process the system diverts to recycle.
Warning - Over Temp Permeate
Water
This warning is generate by means of a digital input
from the Thornton meter when the permeate
temperature is above a set point. If in service and
feeding the process the system diverts to recycle.
Warning - Low Flow - Permeate -
FT4501
This warning is generated if the flow has remained
outside the allowable band for a time.
Warning - High Flow - Permeate -
FT4501
See above
Warning - Low Flow - RO Drain -
FT4001
See above
Warning - High Flow - RO Drain -
FT4001
See above
Warning - Low Flow - RO Recycle
- FT4002
See above
Warning - High Flow - RO Recycle
- FT4002
See above
Warning - Low Flow - RO Twin
Pass - FT4003
See above
Warning - High Flow - RO Twin
Pass - FT4003
See above
Warning - Poor Final Conductivity
The final conductivity reading is above the
configurable set point. If the unit was feeding the
process the feed is diverted to recycle.
Warning - Poor Final Temperature
The final temperature reading is above the
configurable set point. If the unit was feeding the
process the feed is diverted to recycle.
Warning - Poor Final TOC
The final TOC reading is above the configurable set
point. If the unit was feeding the process the feed is
diverted to recycle.
Warning - Salt Tank 1 Low Level
This warning is generated when the low level in the
brine tank become un covered.
Warning - Salt Tank 2 Low Level
This warning is generated when the low level in the
brine tank become un covered.
Warning - UV Energised Input
Failed
The digital input from the contactor powering the UV
control box is not on.
Warning - UV Healthy Input Failed
The digital input from the UV control box has gone
low.
Warning - Analogue Input CDI1
Current Out of Range
This analogue input has remained out of range for 30
seconds. It is either less than 3.75 mA or greater
than 20.25 mA
Warning - Analogue Input CDI1
See above