43
Example – A 120MBH model is to be connected to a heating system as shown in Figure 9.2. A total of 20 ft of straight pipe
will be installed between the boiler and the system loop.
Count all fittings in the boiler loop (shaded in Figure 9.2):
4 90 Elbows
2 Turn in Tee (under boiler- primary-secondary tees not counted)
2 Isolation Valves
1 Y Strainer having a Cv of 30.
Note: Unions, Secondary Connection Tees, and factory supplied fittings are ignored.
Calculate total equivalent length from Table 9.4:
20ft Straight Pipe + 4 Elbows x 2.8 + 2 Turn in Tee x 5.5 + 2 Valves x 0.7 = 43.6 Equivalent Feet
Since the total equivalent length is less than 60ft, flow through boiler loop meets requirements in Table 9.1
3) Indirect Water Heater Loop Piping – If an indirect water heater is used, install it as shown in Figures 9.3a or 9.3b. Refer to
the indirect water heater installation manual for the proper sizing of the indirect water heater loop pump and piping.
4) Hydraulic Separators – Hydraulic separators serve the same purpose as the closely spaced tees connecting the boiler and
system loops in Figure 9.1. They also generally provide effective connection points for automatic air elimination devices
and an expansion tank. These separators are available from several sources and may be used in place of the closely spaced
tees shown in Figures 9.2, 9.3a or 9.3b. When a hydraulic separator is used in place of the tees, the 60ft equivalent length
limitation still applies. Select a hydraulic separator having 1” or larger boiler connections that is designed for the boiler flow
rates shown in Table 9.1.
Table 9.4: Equivalent Lengths for Selected Valves and Fittings
(May Be Used for Copper or Threaded Fittings)
Fitting
Pipe Size
Equivalent Length (ft)
90° Elbow
1”
2.8
45° Elbow
1”
1.4
90° Turn in Tee
1”
5.5
Run of Tee
1”
1.8
Gate Valve (Open)
1”
0.7
Full Port Ball Valve
1”
0.7
Y-Strainer*
1”
7.0
* Based on Cv of 20. Pressure drop through strainers varies widely. 7ft equivalent length may be
assumed for strainers having a published Cv greater than 20.
Table 9.5: Flow Available with Boiler Loop Equivalent Length of 60ft or Less*
Boiler Model
Approx. Flow
(GPM)
Approx. Rise (°F)
Circulator Model
Taco
Grundfos
80MBH
6.4
23
009
26-64
100MBH
8.0
23
0013
26-99
120MBH
9.2
24
0013
26-99
150MBH
11.9
24
0013
26-99
180MBH
11.9
29
0013
26-99
* For multi-speed pumps, this table assumes pump is set to highest speed.
Summary of Contents for Shadow Series
Page 10: ...9 Figure 5 1 Wall Layout Mounting Hole Location...
Page 11: ...10 Figure 5 2 Boiler Mounting Bracket Installation Boiler Wall Mounting...
Page 17: ...16 FIGURE 7 4 WALL PENETRATION CLEARANCES FOR PVC VENT PIPE...
Page 34: ...33 FIGURE 7 24 INSTALLATION OF IPEX AND DIVERSITECH CONCENTRIC TERMINAL THROUGH ROOF...
Page 41: ...40 FIGURE 9 2 NEAR BOILER PIPING HEATING ONLY BOILER LOOP PIPING SHOWN SHADED...
Page 42: ...41 FIGURE 9 3a NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 43: ...42 FIGURE 9 3b NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 47: ...46 This page is intentionally left blank...
Page 50: ...49 FIGURE 10 2 LINE VOLTAGE FIELD CONNECTIONS FIGURE 10 3 LOW VOLTAGE PCB TERMINAL CONNECTIONS...
Page 52: ...51 FIGURE 10 4a 120V LWCO FIELD WIRING FIGURE 10 4b 24V LWCO FIELD WIRING...
Page 54: ...53 FIGURE 10 6 INTERNAL WIRING CONNECTIONS DIAGRAM...
Page 55: ...54...
Page 62: ...61 Lighting and Operating Instructions...
Page 82: ...81 FIGURE 14 6 CONTROLS LOCATION FIGURE 14 7 PRESSURE SWITCH TUBING CONNECTIONS...
Page 87: ...86 Blower Gas Valve Assembly for 150 180...
Page 90: ...89...
Page 103: ...102...