6
4) All boilers are shipped from the factory configured for use with natural gas. They may be converted for use with LP gas
(“propane”) using a combustion analyzer in accordance with the instructions in Appendix A.
5) Models are not suitable for installation at altitudes above 2000ft.
IV Locating the Boiler
1) Observe the minimum clearances shown in Figure 4.1. These clearances apply to combustible construction as well as non-
combustible walls, floors, ceilings and doors.
2) Note the recommended service clearances in Figure 4.1. These service clearances are recommended, but may be reduced to
the combustible clearances provided:
a. Access to the front of the boiler is provided through a door.
b. Access is provided to the condensate trap located beneath the boiler.
Note that servicing the boiler will become increasingly difficult as these service clearances are reduced.
3) Observe the following clearances from piping to combustible construction:
Non-concentric vent (exhaust): ¼”
Air intake piping: 0”
Hot water piping: ¼”
4) The relief valve and gauge must be installed in the location shown in Figure 2.1 and must be in the same space as the boiler.
5) The boiler should be located so as to minimize the length of the vent system.
6) The combustion air piping must terminate where outdoor air is available for combustion and away from areas that will con-
taminate combustion air. Avoid areas near chemical products containing chlorine, chloride based salts, chloro/fluorocarbons,
paint removers, cleaning solvents and detergents.
NOTICE
This product must be installed by a licensed plumber or gas fitter when
installed within the Commonwealth of Massachusetts. See Appendix B for
additional important information about installing this product within the
Commonwealth of Massachusetts.
DANGER
•
Do not attempt to operate this boiler on LP gas without converting it in accordance with the
instructions shown in Appendix A.
•
Do not attempt to convert this boiler to LP gas without the use of a combustion analyzer.
•
Failure to follow the conversion instructions in Appendix A will result in operation of the boil-
er at unsafe Carbon Monoxide (CO) levels and may result in personal injury or loss of life.
Improper conversion may also result in unreliable operation, resulting in property damage.
WARNING
Do not install this boiler at altitudes above 2000ft. Attempting to do so may result in unreliable
operation, property damage, personal injury or loss of life.
Summary of Contents for Shadow Series
Page 10: ...9 Figure 5 1 Wall Layout Mounting Hole Location...
Page 11: ...10 Figure 5 2 Boiler Mounting Bracket Installation Boiler Wall Mounting...
Page 17: ...16 FIGURE 7 4 WALL PENETRATION CLEARANCES FOR PVC VENT PIPE...
Page 34: ...33 FIGURE 7 24 INSTALLATION OF IPEX AND DIVERSITECH CONCENTRIC TERMINAL THROUGH ROOF...
Page 41: ...40 FIGURE 9 2 NEAR BOILER PIPING HEATING ONLY BOILER LOOP PIPING SHOWN SHADED...
Page 42: ...41 FIGURE 9 3a NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 43: ...42 FIGURE 9 3b NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 47: ...46 This page is intentionally left blank...
Page 50: ...49 FIGURE 10 2 LINE VOLTAGE FIELD CONNECTIONS FIGURE 10 3 LOW VOLTAGE PCB TERMINAL CONNECTIONS...
Page 52: ...51 FIGURE 10 4a 120V LWCO FIELD WIRING FIGURE 10 4b 24V LWCO FIELD WIRING...
Page 54: ...53 FIGURE 10 6 INTERNAL WIRING CONNECTIONS DIAGRAM...
Page 55: ...54...
Page 62: ...61 Lighting and Operating Instructions...
Page 82: ...81 FIGURE 14 6 CONTROLS LOCATION FIGURE 14 7 PRESSURE SWITCH TUBING CONNECTIONS...
Page 87: ...86 Blower Gas Valve Assembly for 150 180...
Page 90: ...89...
Page 103: ...102...