56
NOTICE
To minimize the risk of premature heat exchanger failure, observe the following water chemistry
requirements:
1) Minimize the introduction of make-up water, dissolved oxygen, and contaminants into the boiler by
following the installation guidelines shown in the Water Quality and Boiler Water Additives Note on Page 38.
2) Make sure the system is fi lled with water meeting the following criteria:
• pH between 6.5 and 9.5 (for systems containing aluminum components, between 6.5 and 8.5)
• Chloride level less than 200PPM. If fi ll water is drawn from a system containing a water
softener, test a sample of the fi ll water to confi rm that this criteria is met.
• Hardness less than 7 grains/gallon.
3) Avoid the use of petroleum based boiler additives. These can attack seals in both the boiler and system.
4) If freeze protection is required, use the following or its equivalent:
• Fernox Alphi -11 (inhibited Propylene Glycol) available from Alent plc Consumer Products Division,
4100 6th Avenue, Altoona PA. (972) 547 6002 ([email protected]).
Refer to the antifreeze manufacturer’s instructions for required dosage. In general these products are a
blend of glycol (for freeze protection) and inhibitors (to protect the glycol from attacking metallic system
components). Do not add any more antifreeze than is necessary to protect the system from freeze damage.
Many of these products require annual testing of the system water to ensure that the inhibitors are still
active; consult the manufacturer’s instructions for maintenance requirements. Allowance must be made for
the additional expansion of the glycol solution.
5) For system cleaning, use the following or its equivalent:
• Fernox Cleaner F3 available from Alent plc Consumer Products Division, 4100 6th Avenue, Altoona PA.
(972) 547 6002 ([email protected]).
Refer to the instructions supplied with the cleaner for proper dosage and use.
DANGER
Asphyxiation Hazard. Failure to properly convert this boiler for use on lp gas can cause unreliable
operation at elevated carbon monoxide (CO) levels, resulting in personal injury or death.
WARNING
Poison Hazard. Use only inhibited propylene glycol solutions specifi cally formulated for hydronic
systems. Do not use ethylene glycol, which is toxic and can attack gaskets and seals used in
hydronic systems. Use of ethylene glycol could result in property damage, personal injury or death.
Summary of Contents for Shadow Series
Page 10: ...9 Figure 5 1 Wall Layout Mounting Hole Location...
Page 11: ...10 Figure 5 2 Boiler Mounting Bracket Installation Boiler Wall Mounting...
Page 17: ...16 FIGURE 7 4 WALL PENETRATION CLEARANCES FOR PVC VENT PIPE...
Page 34: ...33 FIGURE 7 24 INSTALLATION OF IPEX AND DIVERSITECH CONCENTRIC TERMINAL THROUGH ROOF...
Page 41: ...40 FIGURE 9 2 NEAR BOILER PIPING HEATING ONLY BOILER LOOP PIPING SHOWN SHADED...
Page 42: ...41 FIGURE 9 3a NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 43: ...42 FIGURE 9 3b NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 47: ...46 This page is intentionally left blank...
Page 50: ...49 FIGURE 10 2 LINE VOLTAGE FIELD CONNECTIONS FIGURE 10 3 LOW VOLTAGE PCB TERMINAL CONNECTIONS...
Page 52: ...51 FIGURE 10 4a 120V LWCO FIELD WIRING FIGURE 10 4b 24V LWCO FIELD WIRING...
Page 54: ...53 FIGURE 10 6 INTERNAL WIRING CONNECTIONS DIAGRAM...
Page 55: ...54...
Page 62: ...61 Lighting and Operating Instructions...
Page 82: ...81 FIGURE 14 6 CONTROLS LOCATION FIGURE 14 7 PRESSURE SWITCH TUBING CONNECTIONS...
Page 87: ...86 Blower Gas Valve Assembly for 150 180...
Page 90: ...89...
Page 103: ...102...