66
TABLE 12.4: Default Settings and Ranges
Scr. # Description on Screen
Description
Default Value Allowable Range
S0
“F” or “C”
Temperature Units
F
F or C
S1
“CH”
Heating set point (max temperature
set-point upon a call for space heat) 180F
32 - 191F
S2
“Odr”
Outdoor Reset Enable
On
On or Off
S3
“LBT”
Low boiler temp (Fig 12.3)
130F
69 - 191F
S4
“HOD”
High outdoor temp (Fig 12.3)
70F
31 - 101F
S5
“LOD”
Low outdoor temp (Fig 12.3)
0F
-40 - 100F
S6
“dH”
Boiler water set point on call for
domestic hot water
170F
32 - 191F
S7
ASC
Anti short cycle time
0
0 - 15m
FIGURE 12.3: OUTDOOR RESET CURVE (DEFAULT SETTINGS SHOWN)
Summary of Contents for Shadow Series
Page 10: ...9 Figure 5 1 Wall Layout Mounting Hole Location...
Page 11: ...10 Figure 5 2 Boiler Mounting Bracket Installation Boiler Wall Mounting...
Page 17: ...16 FIGURE 7 4 WALL PENETRATION CLEARANCES FOR PVC VENT PIPE...
Page 34: ...33 FIGURE 7 24 INSTALLATION OF IPEX AND DIVERSITECH CONCENTRIC TERMINAL THROUGH ROOF...
Page 41: ...40 FIGURE 9 2 NEAR BOILER PIPING HEATING ONLY BOILER LOOP PIPING SHOWN SHADED...
Page 42: ...41 FIGURE 9 3a NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 43: ...42 FIGURE 9 3b NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 47: ...46 This page is intentionally left blank...
Page 50: ...49 FIGURE 10 2 LINE VOLTAGE FIELD CONNECTIONS FIGURE 10 3 LOW VOLTAGE PCB TERMINAL CONNECTIONS...
Page 52: ...51 FIGURE 10 4a 120V LWCO FIELD WIRING FIGURE 10 4b 24V LWCO FIELD WIRING...
Page 54: ...53 FIGURE 10 6 INTERNAL WIRING CONNECTIONS DIAGRAM...
Page 55: ...54...
Page 62: ...61 Lighting and Operating Instructions...
Page 82: ...81 FIGURE 14 6 CONTROLS LOCATION FIGURE 14 7 PRESSURE SWITCH TUBING CONNECTIONS...
Page 87: ...86 Blower Gas Valve Assembly for 150 180...
Page 90: ...89...
Page 103: ...102...