101
FIGURE C.4: PIM ERROR CODES
Code
Meaning
Possible Causes/Remedies
E81
Password not recognized.
Correct display does not require a password, so this is a possible indication of incompatible display or control.
If either has been replaced, verify that it is the correct type specified by the parts list in manual. Try upload
again. If problem persists, consult factory.
E82
PIM not detected in socket
Improperly seated or missing PIM.
E85
PIM is not compatible with the control
Either PIM or replacement control is not intended for use on this boiler. Check part numbers on both with
replacement parts list in manual.
E88
Command from display not recognized
Try upload again, if problem persists, replace display.
E98
Timeout
Possible indication of incompatible display. If display has been replaced, verify that it is the correct type speci-
fied by the parts list in manual. If problem persists, replace PIM.
E83, E84,
E87, E89
Various
These errors should never occur on this boiler. If one appears, verify compatibility of control, PIM, and display
(all should match what is shown in the parts list in manual). Try upload again. If problem persists, consult
factory.
FIGURE C3: UPLOADING PIM DATA TO CONTROL
From
Home
Screen
To Home
Screen
Upload
successful?
Yes
No
Confirm
Error code
appears if
upload fails.
See Table C.4
for a list of
codes
“rES” flashes during
upload process
Press RH (“Confirm”)
to start uploading
process
“rES” stops
Flashing if
upload
successful
Summary of Contents for Shadow Series
Page 10: ...9 Figure 5 1 Wall Layout Mounting Hole Location...
Page 11: ...10 Figure 5 2 Boiler Mounting Bracket Installation Boiler Wall Mounting...
Page 17: ...16 FIGURE 7 4 WALL PENETRATION CLEARANCES FOR PVC VENT PIPE...
Page 34: ...33 FIGURE 7 24 INSTALLATION OF IPEX AND DIVERSITECH CONCENTRIC TERMINAL THROUGH ROOF...
Page 41: ...40 FIGURE 9 2 NEAR BOILER PIPING HEATING ONLY BOILER LOOP PIPING SHOWN SHADED...
Page 42: ...41 FIGURE 9 3a NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 43: ...42 FIGURE 9 3b NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 47: ...46 This page is intentionally left blank...
Page 50: ...49 FIGURE 10 2 LINE VOLTAGE FIELD CONNECTIONS FIGURE 10 3 LOW VOLTAGE PCB TERMINAL CONNECTIONS...
Page 52: ...51 FIGURE 10 4a 120V LWCO FIELD WIRING FIGURE 10 4b 24V LWCO FIELD WIRING...
Page 54: ...53 FIGURE 10 6 INTERNAL WIRING CONNECTIONS DIAGRAM...
Page 55: ...54...
Page 62: ...61 Lighting and Operating Instructions...
Page 82: ...81 FIGURE 14 6 CONTROLS LOCATION FIGURE 14 7 PRESSURE SWITCH TUBING CONNECTIONS...
Page 87: ...86 Blower Gas Valve Assembly for 150 180...
Page 90: ...89...
Page 103: ...102...