48
FIGURE 10.1: LOCATION OF HIGH AND LOW VOLTAGE FIELD ELECTRICAL CONNECTIONS
The use of the pump outputs are as follows:
a) Boiler pump - Pumps water through the boiler. It is on whenever there is a call for CH or DHW.
b) DHW Pump (“IWH Circulator”) - Pumps water directly through the indirect water heater.
c) System Pump - Pumps water through the radiation. This pump is hydraulically separated from the boiler pump, either by
closely spaced tees, or by a hydraulic separator. The system pump is always on when the system is responding to a call
for CH.
Maximum combined current draw for all circulators is 6.3 FLA.
2) Low Voltage Connections
– Low voltage field connections on the low voltage PCB are shown in Figure 10.3 and are listed
from left to right:
1 Heat T’Stat - 24VAC heating thermostat
2 Heat T’Stat - 24VAC heating thermostat
3 DHW Stat - 24VAC domestic hot water thermostat (1)
4 DHW Stat - 24VAC domestic hot water thermostat (2)
5 External Limit - Field supplied low voltage safety limit contacts (1)
6 External Limit - Field supplied low voltage safety limit contacts (2)
7 Outdoor Sensor - Tasseron TSA00AA Outdoor Temperature Sensor (1)
8 Outdoor Sensor - Tasseron TSA00AA Outdoor Temperature Sensor (2)
External power must not be applied to any of the low voltage terminals - doing so may damage the boiler control. Also note
the following:
a) External Limit
- The external limit terminals are intended for use with a field supplied safety device, such as a manual
reset high limit or low-water cut-off. When an external limit is used, the jumper between these two terminals must be
removed. Failure to remove this jumper will render the external safety devices ineffective.
Summary of Contents for Shadow Series
Page 10: ...9 Figure 5 1 Wall Layout Mounting Hole Location...
Page 11: ...10 Figure 5 2 Boiler Mounting Bracket Installation Boiler Wall Mounting...
Page 17: ...16 FIGURE 7 4 WALL PENETRATION CLEARANCES FOR PVC VENT PIPE...
Page 34: ...33 FIGURE 7 24 INSTALLATION OF IPEX AND DIVERSITECH CONCENTRIC TERMINAL THROUGH ROOF...
Page 41: ...40 FIGURE 9 2 NEAR BOILER PIPING HEATING ONLY BOILER LOOP PIPING SHOWN SHADED...
Page 42: ...41 FIGURE 9 3a NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 43: ...42 FIGURE 9 3b NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 47: ...46 This page is intentionally left blank...
Page 50: ...49 FIGURE 10 2 LINE VOLTAGE FIELD CONNECTIONS FIGURE 10 3 LOW VOLTAGE PCB TERMINAL CONNECTIONS...
Page 52: ...51 FIGURE 10 4a 120V LWCO FIELD WIRING FIGURE 10 4b 24V LWCO FIELD WIRING...
Page 54: ...53 FIGURE 10 6 INTERNAL WIRING CONNECTIONS DIAGRAM...
Page 55: ...54...
Page 62: ...61 Lighting and Operating Instructions...
Page 82: ...81 FIGURE 14 6 CONTROLS LOCATION FIGURE 14 7 PRESSURE SWITCH TUBING CONNECTIONS...
Page 87: ...86 Blower Gas Valve Assembly for 150 180...
Page 90: ...89...
Page 103: ...102...