When CPVC and/or PVC pipe is used, it must be joined using primer and cement that is listed for use with the pipe material
being joined (PVC, CPVC, or CPVC to PVC).
2. Vent Kits Available for Use with this Boiler
– The following vent kits are available for CPVC/PVC vent systems installed
with this boiler in the USA:
•
107039-01 - 2” CPVC/PVC Vent Kit
•
107039-02 – 3” CPVC/PVC Vent Kit
These kits include the following:
(1)
30” CPVC Straight Pipe
(1)
90 degree short bend CPVC Elbow
(1)
Straight PVC Coupling (for exhaust terminal)
(1)
90 degree PVC Elbow (for intake termination)
(2)
Rodent screens
The CPVC Pipe and elbow supplied with these kits are not listed to ULC S636 and may not be used in Canada.
3. Maximum Vent and Air Intake Lengths - The maximum length of the vent/air intake piping depends upon the vent option
selected and the boiler size.
See Tables 7.5, 7.11 or 7.15
for the maximum vent lengths. These maximum lengths apply
to both the vent and intake piping (e.g. Option 1 may have up to 60ft of intake and 60ft of vent piping). For all vent
systems, the lengths shown in Tables 7.5, 7.11 and 7.15 are in addition to the first 90° elbow. If more elbows are desired,
the maximum allowable vent length must be reduced by the amount shown in Table
7.1
for each additional elbow used.
Termination fittings are never counted.
It is recommended that all field supplied PVC or CPVC elbows be “1/4 Bend” (Sanitary 90° El) or “Long Sweep 1/4 Bend”
type elbows (Figure 7.2). In this manual “sanitary” and “long sweep” elbows are treated as having the same equivalent
length.
Example:
A 3” twin pipe horizontal CPVC/PVC vent system is planned for a horizontally vented 120MBH model which has the
following components in the vent system:
•
1 ft CPVC Straight Pipe
•
90 CPVC Elbow (short bend)
•
1-1/2 ft CPVC Straight Pipe
•
Coupling
•
10 ft PVC Straight Pipe
•
90 PVC Elbow (Sanitary Elbow Design)
•
15 ft PVC Straight Pipe
•
PVC Coupling Terminal
The Vent Option #2 column in Table 7.5 describes a horizontal direct vent system using 3” CPVC and PVC pipe. From this
column, we see that the boiler may have a vent length of up to 135ft. The first CPVC 90 degree elbow is not considered. From
Table 7.1, we see that the equivalent length of the 90 PVC elbow is 4ft and that the equivalent length of the coupling is 0ft.
The total equivalent length of the planned venting system is therefore:
1ft (Straight CPVC) + 0ft (first short bend CPVC 90 Elbow) + 1.5ft (Straight CPVC) + 0ft (Coupling) + 10ft (Straight PVC)
+ 4ft (PVC 90 Sanitary Elbow) + 15ft (Straight PVC) + 0ft (Coupling Terminal) = 31.5ft.
Since Table 7.5 shows a maximum allowable vent length of 135ft, the planned vent system length is acceptable
NOTICE
Do not exceed maximum vent/combustion air system length. Refer to Tables 7.5, 7.11 and 7.15 in this
section for maximum vent/combustion air system length.
Use only vent and combustion air terminals and terminal locations shown in Tables 7.5, 7.11 and 7.15
and related Figures.
NOTICE
When 3” venting is used with the 80 or 100 models, a 2” x 3” CPVC Increaser and a short length of 2”
CPVC pipe will be required to adapt from the 2” vent collar to the 3” components in the 107039-02 kit.
These items are not included in the kit itself.
Summary of Contents for Shadow Series
Page 10: ...9 Figure 5 1 Wall Layout Mounting Hole Location...
Page 11: ...10 Figure 5 2 Boiler Mounting Bracket Installation Boiler Wall Mounting...
Page 17: ...16 FIGURE 7 4 WALL PENETRATION CLEARANCES FOR PVC VENT PIPE...
Page 34: ...33 FIGURE 7 24 INSTALLATION OF IPEX AND DIVERSITECH CONCENTRIC TERMINAL THROUGH ROOF...
Page 41: ...40 FIGURE 9 2 NEAR BOILER PIPING HEATING ONLY BOILER LOOP PIPING SHOWN SHADED...
Page 42: ...41 FIGURE 9 3a NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 43: ...42 FIGURE 9 3b NEAR BOILER PIPING HEATING PLUS INDIRECT WATER HEATER...
Page 47: ...46 This page is intentionally left blank...
Page 50: ...49 FIGURE 10 2 LINE VOLTAGE FIELD CONNECTIONS FIGURE 10 3 LOW VOLTAGE PCB TERMINAL CONNECTIONS...
Page 52: ...51 FIGURE 10 4a 120V LWCO FIELD WIRING FIGURE 10 4b 24V LWCO FIELD WIRING...
Page 54: ...53 FIGURE 10 6 INTERNAL WIRING CONNECTIONS DIAGRAM...
Page 55: ...54...
Page 62: ...61 Lighting and Operating Instructions...
Page 82: ...81 FIGURE 14 6 CONTROLS LOCATION FIGURE 14 7 PRESSURE SWITCH TUBING CONNECTIONS...
Page 87: ...86 Blower Gas Valve Assembly for 150 180...
Page 90: ...89...
Page 103: ...102...