VAMP Ltd
Feeder and motor manager
Technical description
VAMP 257
VM257.EN002
VAMP 24h support phone : +358 (0)20 753 3264
57
Parameter Value Unit
Description
Shot#
1 … 5
-
The
currently
running shot
ReclT RECLAIMTIME;
STARTTIME;
DEADTIME;
DISCRIMINATIONTIME
-
The
currently
running time
(or last
executed)
SCntr
-
Total start
counter
Fail
-
The counter
for failed AR
shots
Shot1 *
-
Shot1 start
counter
Shot2 *
-
Shot2 start
counter
Shot3 *
-
Shot3 start
counter
Shot4 *
-
Shot4 start
counter
Measured
or
recorded
values
Shot5 *
-
Shot5 start
counter
*) There are 5 counters available for each one of the four AR signals.
Cu
rrent
S
tart
d
e
l
a
y
1
D
ea
d
Time1
D
ea
d
Time2
D
is
c
rimination
time1
D
is
c
rimination
time2
R
e
cl
aim
time
Open
CB
Cl
ose
CB
CB
open state
CBcl
ose state
I>
settin
g
1
2
3
4
5
6
7
8
9
10
AR
si
g
na
l
s
Figure 2.3.16-2. Example sequence of two shots. After shot 2 the fault is
cleared.
1.
Current exceeds the I> setting; the start delay from shot 1
starts.
2.
After the start delay, an OpenCB relay output closes.
3.
A CB opens. The dead time from shot 1 starts, and the
OpenCB relay output opens.
4.
The dead time from shot 1 runs out; a CloseCB output
relay closes.