VAMP 257
Feeder and motor manager
Operation and configuration
VAMP Ltd
40
VAMP 24h support phone +358 (0)20 753 3264
VM257.EN002
7.
Commissioning configuration
7.1.
Factory settings
When delivered from the factory, the manager has got either
factory default settings or settings defined by the customer.
The configuration can be read from the workshop test reports
or from the final test reports.
7.1.1.
Configuration during commissioning
The settings of the manager can be defined and checked during
the commissioning in accordance with the instructions given in
chapter 5 of this manual. The order can be, for example, the
following:
1.
The scaling of the rated values of the phase currents
(CONF/CURRENT SCALING menu)
2.
The scaling of the rated values of the voltages
(CONF/VOLTAGE SCALING menu)
The scaling is done in the software block of the measured
signals (see Figure 7.1.1-1). Thus, the scaling will affect all the
protection functions.
Figure 7.1.1-1. Principle for scaling the measured values of the manager
3.
The activation of the desired protection functions, Prot
menu. See chapter 5.5.
4.
The setting values of the protection function parameters
(e.g. I> menu). See chapter 5.6 on page 33.
5.
The routing of the trip and alarm signals from the
protection functions to the desired output relays and LED
indicators (DO menu). See chapter 5.4 on page 32.
6.
The configuration of the blocking matrix (VAMPSET
software).
7.
The configuration of the desired DI inputs, for example
external blockings (DI menu). See chapter 5.3 on page 32.
8.
Configuration of communication parameters (Bus menu).
See chapter 5.8 on page 35.
9.
Drawing of the mimic picture.