Parameter Value
Unit Default Description
T_Off
Enabled;
Disabled
-
Enabled Trip off event
Measured and recorded values of unbalanced load
function:
I
2
/I
1
> (46)
Parameter Value Unit Description
Measured
value
I2/I1
%
Relative negative sequence
component
SCntr
Cumulative
start
counter
TCntr
Cumulative
start
counter
Flt
%
Maximum
I
2
/I
1
fault component
Recorded
values
EDly
%
Elapsed time as compared to
the set operating time, 100% =
tripping
2.3.6.
Unbalance protection (46)
NOTE!
This function is available only in motor protection mode.
The unbalance stage protects the motor against unbalanced
phase currents and single phasing. The protection is based on
the negative sequence current.
Both definite time and inverse time characteristics are
available. The inverse delay is based on Equation 2.3.6-1. Only
the base frequency components of the phase currents are used
to calculate the negative sequence value I
o
.
Equation 2.3.6-1
2
2
2
2
1
)
(
K
I
I
K
T
MOT
−
=
where,
T
= Operation time
K
1
= Thermal time constant of the rotor (I
22
t value)
I
2
= Negative sequence phase current, base frequency
component
I
MOT
= Nominal current of the motor
K
2
= The maximum allowed degree of unbalance