3.2.
Setting groups
Most of the protection functions of the manager have two
setting groups. These groups are useful for example when the
network topology is changed frequently. The active group can
be changed by a digital input, through remote communication
or locally by using the local panel.
The active setting group of each protection function can be
selected separately. Figure 3.2-1 shows an example where the
changing of the I> setting group is handled with digital input
one (SGrpDI). If the digital input is TRUE, the active setting
group is group two and correspondingly, the active group is
group one, if the digital input is FALSE. If no digital input is
selected (SGrpDI = -), the active group can be selected by
changing the value of the parameter SetGrp.
Figure 3.2-1. Example of protection submenu with setting group parameters
The changing of the setting parameters can be done easily.
When the desired submenu has been found (with the arrow
keys), press the ENTER key to select the submenu. Now the
selected setting group is indicated in the down-left corner of the
display (See Figure 3.2-2). Set1 is setting group one and Set2 is
setting group two. When the needed changes, to the selected
setting group, have been done, press the LEFT or the RIGHT
key to select another group (the LEFT key is used when the
active setting group is 2 and the RIGHT key is used when the
active setting group is 1).
Figure 3.2-2. Example of I> setting submenu