3.4.
Operating levels
The manager has three operating levels:
User level
,
Operator
level
and
Configuration level
. The purpose of the operating
levels is to prevent accidental change of manager
configurations, parameters or settings.
USER level
Use:
Possible to read e.g. parameter values,
measurements and events
Opening:
Level permanently open
Closing:
Closing not possible
OPERATOR level
Use:
Possible to control objects and to change e.g.
the settings of the protection stages
Opening:
Default password 0001
Setting state: Push ENTER
Closing:
The level is automatically closed after 10
minutes idle time. Giving the password 9999
can also close the level.
CONFIGURATION level
Use:
The configuration level is needed during the
commissioning of the manager. E.g. the
scaling of the voltage and current
transformers can be set.
Opening:
Default password 0002
Setting state: Push ENTER
Closing:
The level is automatically closed after 10
minutes idle time. Giving the password 9999
can also close the level.