VAMP Ltd
Feeder and motor manager
Operation and configuration
VAMP 257
VM257.EN002
VAMP 24h support phone +358 (0)20 753 3264
29
5.
Configuration and parameter
setting
Operating level: CONFIGURATION
•
Choose and configure the digital inputs in the DI submenu.
•
Configure the digital outputs in the DO submenu.
•
Select the needed protection functions in the Prot submenu.
•
Set the ”Device Setup”, the scaling (for example I
nom
, I
sec
,
etc.) and the date and time in the CONF submenu.
•
Change the parameters of the protection functions in the
function-related submenus, for example I>.
•
Choose and configure the communication buses in the Bus
submenu.
•
Configure interlockings for objects and protection functions
with the VAMPSET software.
Some of the parameters can only be changed via the RS-232
serial port using the VAMPSET software. Such parameters,
(for example passwords, blockings and mimic configuration) are
normally set only during commissioning.
Some of the parameters require the restarting of the manager.
This restarting is done automatically when necessary. If a
parameter is tried to change the manager will inform about the
auto-reset feature (see Figure 5-1).
Figure 5-1. Example of auto-reset display
Press CANCEL to return to the setting view. If a parameter
must be changed, press the ENTER key again. The parameter
can now be set. When the parameter change is confirmed with
the ENTER key, a [RESTART]- text appears to the top-right
corner of the display. This means that auto-resetting is
pending. If no key is pressed, the auto-reset will be executed
within few seconds.